Plan Review Notes
Plan Review Notes For Permit 10120402
Permit Number 10120402
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-12-21 17:34:35700 SOUTH ROSEMARY AVENUE, SUITE #204
 PERMIT #10120402
 MASTER #10090192
 REVIEW COMMENTS - FIRE
  
  
 PROVIDE HYDRAULIC CALCULATIONS SUPPORTING USE OF
 FLEXIBLE SPRINKLER DROPS.
  
 INDICATE THE MAXIMUM NUMBER OF BENDS AND THE MINIMUM
 BEND RADIUS OF THE FLEXIBLE DROPS.
  
 SIDEWALL SPRINKLERS ARE PENETRATING A 2-HOUR FIRE RATED
 PARTITION WALL IN CABANA SEATING #107. VERIFY
 SEMI-RECESSED SIDEWALL SPRINKLERS ARE UL LISTED TO BE
 LOCATED IN A FIRE RATED WALL ASSEMBLY.
  
 INDICATE IF SPRINKLER PROTECTION WILL BE PROVIDED IN
 THE CONCEALED SPACES BELOW THE RAISED PLATFORMS.
  
 INDICATE THE LOCATION OF THE SHUTOFF VALVE CONTROLLING
 THE SPRINKLERS IN THIS SPACE.
  
 A SIDEWALL SPRINKLER INSTALLED BELOW THE TIKI CANOPY IS
 LOCATED 14 FEET FROM THE WALL.
  
 DECORATE COLUMN PALM LEAVES (X4) APPEAR TO CREATE A
 SPRINKLER SPRAY OBSTRUCTION IN THE MAIN DANCE FLOOR
 AREA.
  
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW