Plan Review Notes
Plan Review Notes For Permit 10120362
Permit Number 10120362
Review Stop E
Sequence Number 1
Notes
Date Text
2011-01-05 13:48:32LIST THE NUMBER OF CONDUCTORS INCLUDING THE NEUTRAL AND
 EQUIPMENT BONDING (GROUND) CONDUCTOR SIZES FEEDING THE
 60 AMP PANEL. SPECIFY THE GROUNDING ELECTRODE TO BE
 USED. NEC 250.32 (A) AND (B), TABLE 250.122
 SPECIFY THE TYPE OF CONDUIT TO BE UTILIZED AND THE NEMA
 CLASSIFICATION FOR THE OUTSIDE DISCONNECT. NEC 110.11
 PROVIDE A PANEL SCHEDULE LISTING THE NUMBER OF
 CIRCUITS, WIRE SIZE AND OVERCURRENT PROTECTION. NEC
 210.3
 NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT
 RECEPTACLES IN RESIDENTIAL OCCUPANCIES. NEC 406.11
  
 ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718