1 |
|
Notes |
Date |
Text |
2011-01-03 10:25:05 | RESIDENTIAL (R3) ALTERATION/REPAIRS MECHANICAL REVIEW. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PROVIDE COMPLETE HEATING AND COOLING CALCULATIONS AS | | REQUIRED BY SEC. RM1401.3 AND SEC. N1107 OF 2007 | | FLORIDA RESIDENTIAL CODE. | | | | 2- PROVIDE COMPLETE HVAC PLANS WITH COMPLETE EQUIPMENT | | INFORMATION. SHOW ALL EQUIPMENT LOCATION AND SPECIFY | | ALL CFM'S. | | | | 3- SPECIFY BATHROOM VENTILATION AS REQUIRED BY SEC. | | M1507.1 | | | | 4- A) RETURN AIR GRILL IS NOT ALLOWED IN THE BATHROOM. | | SEC. M1602.2. REVISE DRAWING ON SHEET A-1.2. | | | | B) SPECIFY RETURN AIR ON BEDROOM. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | | | | | |
|