Plan Review Notes
Plan Review Notes For Permit 10120354
Permit Number 10120354
Review Stop M
Sequence Number 1
Notes
Date Text
2011-01-03 10:25:05RESIDENTIAL (R3) ALTERATION/REPAIRS MECHANICAL REVIEW.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE COMPLETE HEATING AND COOLING CALCULATIONS AS
 REQUIRED BY SEC. RM1401.3 AND SEC. N1107 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE COMPLETE HVAC PLANS WITH COMPLETE EQUIPMENT
 INFORMATION. SHOW ALL EQUIPMENT LOCATION AND SPECIFY
 ALL CFM'S.
  
 3- SPECIFY BATHROOM VENTILATION AS REQUIRED BY SEC.
 M1507.1
  
 4- A) RETURN AIR GRILL IS NOT ALLOWED IN THE BATHROOM.
 SEC. M1602.2. REVISE DRAWING ON SHEET A-1.2.
  
 B) SPECIFY RETURN AIR ON BEDROOM.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  
  