Notes |
Date |
Text |
2011-01-11 14:10:32 | 2007 FBC W/2009 REVISIONS | | 2008 NEC | | | | DENIED BY ELECTRICAL | | | | 1) SHOW COMPLIANCE WITH NEC 210.70 (A)(2)(B) SWITCH | | CONTROLLED LIGHTING OUTLET REQUIRED AT EXTERIOR | | ENTRANCES. | | | | 2) SHOW COMPLIANCE WITH NEC 210.52(E)(1) AT LEAST ONE | | RECEPTACLE OUTLET NOT MORE THAN 6 - 1/2 FEET ABOVE | | GRADE IS REQUIRED AT THE FRONT AND BACK OF THE | | DWELLING. | | | | 3) SHOW COMPLIANCE WITH NEC 406.8 WEATHER PROOF | | ENCLOSURE IN WET LOCATIONS. | | | | 4) SHOW COMPLIANCE WITH NEC 210.12 AFCI TYPICAL. | | | | 5) SHOW COMPLIANCE WITH NEC 406.11 TAMPER - RESISTANT | | RECEPTACLES TYPICAL. | | | | 6) A SEPARATE PERMIT AND APPLICATION FOR ELECTRIC IS | | REQUIRED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | | | | | | |
|