2010-12-30 11:57:36RESIDENTIAL (R3) ALTERATION/REPAIRS BUILDING REVIEW
 CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- A) SCOPE OF WORK ON PERMIT APPLICATION CALLS FOR
 REPAIRS & ALTERATION DUE TO TERMITE DAMAGE. PLANS
 SUBMITTED DON'T SHOW ANY REPAIRS. ARCHITECT NEED TO
 SPECIFY REPAIRS AND PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS TO SHOW COMPLIANCE WITH THE PROTECTION
 AGAINST DECAY AS REQUIRED BY SEC. R319 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 2- ARCHITECT TO SPECIFY ON PLANS TYPE OF ALTERATION AS
 REQUIRED BY SEC. 401.4 OF 2007 FBC- EXISTING BUILDING
 CODE.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 4- ARCHITECT TO SPECIFY ON PROPOSED FLOOR PLAN HOW
 COMPLYING WITH THE EGRESS REQUIREMENTS OF SEC. R311 AND
 SEC. R310.
  
 5- ARCHITECT TO SPECIFY:
 A) ALL DESIGN LOADS WIND, DEAD AND LIVE LOADS,
 INCLUDING ATTIC LIVE LOADS AS REQUIRED BY SEC. R301 AND
 TABLE R301.5.
  
 B) ALL EXTERIOR OPENINGS DESIGN PRESSURES AS REQUIRED
 BY SEC. R301.
 ***NOTE: ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3
 THIS BUILDIG IS LOCATED ON EXPOSURE "C". TAKE THIS INTO
 CONSIDERATION FOR THE DESIGN PRESSURES CALCULATIONS.
  
 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. REVISE
 VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 PROFESSIONAL ARCHITECT FEES.
  
 7- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ALL EXTERIOR DOORS AS SHOWN ON PLANS (DOOR LEADING
 TO PORCH FROM BEDROOM AND BATHROOM EXTERIOR DOOR).
 PRODUCT APPROVAL SUBMITTED (FL4809-R3) IS MISSING THE
 DRAWINGS SHOWING THE DOORS TO BE USED.
  
 B) ALL WINDOWS AS SHOWN ON PLANS. PRODUCT APPROVAL
 SUBMITTED (FL4765-R3) SUBMITTED IS MISSING THE DRAWINGS
 FOR SPECIFIC WINDOWS TO BE USED.
  
 C) IF DOOR AND WINDOWS TO BE INSTALLED DON'T HAVE
 IMPACT GLASS, THEN SHUTTERS ARE REQUIRED. SEC.
 R301.2.1.2. PROVIDE PRODUCT APPROVALS AND COMPLETE
 INSTALLATION SCHEDULE.
 ***NOTE: EXISTING SHUTTERS CAN'T BE USED IF THEY WERE
 INSTALLED WITHOUT PERMIT. PROVIDE PROOF THAT EXISTING
 SHUTTERS WERE INSTALLED WITH PERMIT UNDER THE FLORIDA
 BUILDING CODE.
  
 D) METAL ROOF AS SHOWN ON PLANS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
  
 8- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 9- ARCHITECT TO PROVIDE COMPLETE FRAMING PLANS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE SCREENED
 PORCH. SPECIFY ALL COLUMNS, BEAMS, STRUCTURAL
 CONNECTORS TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.
  
 10 - ARCHITECT TO PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS FOR THE CONVERSION OF PORCH TO NEW
 BATHROOM. SPECIFY FOOTINGS, PROVIDE COMPLETE FRAMING
 DETAILS AND SPECIFICATIONS TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES OF SEC. R301. SPECIFY ALL
 STRUCTURAL CONNECTORS. PROVIDE COMPLETE WALL SECTION
 PROVIDING ALL THE SPECIFICATIONS TO INTERIOR AND
 EXTERIOR SIDE.
  
 11- ARCHITECT TO PROVIDE IN ALL PLANS ALL THE
 INFORMATION REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 OF FLORIDA STATUTE.
 MISSING THE FIRM LICENSE NUMBER, NAME OF ARCHITECT
 SIGNING THE PLANS, LICENSE NUMBER OF ARCHITECT AND DATE
 WHEN PLANS WERE SEALED.
  
 12- PROVIDE ROOF FRAMING PLAN WITH COMPLETE
 SPECIFICATIONS FOR NEW ROOF OVER THE PROPOSED PORCH.
 SEE SEC. R803.2.3.1 FOR MIN. NAIL TYPE AND SPACING TO
 BE USED FOR THE ROOF SHEATHING IN ALL ROOF ZONES.
  
 13- SPECIFY SAFETY GLASS ON BATHROOM WINDOWS AS
 REQUIRED BY SEC. R308.4.
  
 14- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806.
  
 15- SPECIFY ATTIC ACCESS SIZE AND LOCATION TO COMPLY
 WITH SEC. R807.
  
 16- REVISE ROOF PITCH SHOWN ON NORTH ELEVATION ON SHEET
 A-2.1.
  
 17- SPECIFY ALL DOORS AND WINDOWS TYPES AND SIZES. SEC.
 106.1.1 CITY AMENDMENTS TO FBC.
  
 18- ENERGY CALCULATIONS SHOW CEILING FAN CREDIT.
 SPECIFY ON PLANS CEILING FAN SIZE TO COMPLY WITH TABLE
 C4.2.1.1 OF CHAPTER 11 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 19- PROVIDE COMPLETE FRAMING DETAILS FOR THE
 INSTALLATION THE THE BEDROOM FRENCH DOORS AND SLIDERS
 AS SHOWN ON PLANS TO VERIFY COMPLIANCE WITH SEC. R301.
  
 20- SHEET C-1.0: UPDATE CODE REFERENCED ON THE GENERAL
 NOTES. CURRENT CODE IS THE 2007 FLORIDA RESIDENTIAL
 CODE WITH 2009 REVISIONS.
  
 21: ENERGY CALCULATIONS SUBMITTED:
 A) REVISE FLOOR TYPE. THIS BUILDING DOESN'T HAVE A SLAB
 ON GRADE. SEE PLANS. REVISE FRONT PAGE AND PAGE 2 OF 5.
  
 B) REVISE THE ROOF TYPE SHOWN ON SHEET 2 OF 5. SEE
 PLANS.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 D) FILL ALL THE INFORMATION ON TOP OF THE FORM.
  