2010-12-30 11:57:36 | RESIDENTIAL (R3) ALTERATION/REPAIRS BUILDING REVIEW |
| CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- A) SCOPE OF WORK ON PERMIT APPLICATION CALLS FOR |
| REPAIRS & ALTERATION DUE TO TERMITE DAMAGE. PLANS |
| SUBMITTED DON'T SHOW ANY REPAIRS. ARCHITECT NEED TO |
| SPECIFY REPAIRS AND PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS TO SHOW COMPLIANCE WITH THE PROTECTION |
| AGAINST DECAY AS REQUIRED BY SEC. R319 OF 2007 FLORIDA |
| RESIDENTIAL CODE. |
| |
| 2- ARCHITECT TO SPECIFY ON PLANS TYPE OF ALTERATION AS |
| REQUIRED BY SEC. 401.4 OF 2007 FBC- EXISTING BUILDING |
| CODE. |
| |
| 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| UP. |
| |
| 4- ARCHITECT TO SPECIFY ON PROPOSED FLOOR PLAN HOW |
| COMPLYING WITH THE EGRESS REQUIREMENTS OF SEC. R311 AND |
| SEC. R310. |
| |
| 5- ARCHITECT TO SPECIFY: |
| A) ALL DESIGN LOADS WIND, DEAD AND LIVE LOADS, |
| INCLUDING ATTIC LIVE LOADS AS REQUIRED BY SEC. R301 AND |
| TABLE R301.5. |
| |
| B) ALL EXTERIOR OPENINGS DESIGN PRESSURES AS REQUIRED |
| BY SEC. R301. |
| ***NOTE: ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 |
| THIS BUILDIG IS LOCATED ON EXPOSURE "C". TAKE THIS INTO |
| CONSIDERATION FOR THE DESIGN PRESSURES CALCULATIONS. |
| |
| 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. REVISE |
| VALUATION TO INCLUDE ALL LABOR, MATERIALS AND |
| PROFESSIONAL ARCHITECT FEES. |
| |
| 7- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) ALL EXTERIOR DOORS AS SHOWN ON PLANS (DOOR LEADING |
| TO PORCH FROM BEDROOM AND BATHROOM EXTERIOR DOOR). |
| PRODUCT APPROVAL SUBMITTED (FL4809-R3) IS MISSING THE |
| DRAWINGS SHOWING THE DOORS TO BE USED. |
| |
| B) ALL WINDOWS AS SHOWN ON PLANS. PRODUCT APPROVAL |
| SUBMITTED (FL4765-R3) SUBMITTED IS MISSING THE DRAWINGS |
| FOR SPECIFIC WINDOWS TO BE USED. |
| |
| C) IF DOOR AND WINDOWS TO BE INSTALLED DON'T HAVE |
| IMPACT GLASS, THEN SHUTTERS ARE REQUIRED. SEC. |
| R301.2.1.2. PROVIDE PRODUCT APPROVALS AND COMPLETE |
| INSTALLATION SCHEDULE. |
| ***NOTE: EXISTING SHUTTERS CAN'T BE USED IF THEY WERE |
| INSTALLED WITHOUT PERMIT. PROVIDE PROOF THAT EXISTING |
| SHUTTERS WERE INSTALLED WITH PERMIT UNDER THE FLORIDA |
| BUILDING CODE. |
| |
| D) METAL ROOF AS SHOWN ON PLANS. |
| |
| E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS. |
| |
| 8- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| |
| 9- ARCHITECT TO PROVIDE COMPLETE FRAMING PLANS AND |
| SPECIFICATIONS FOR THE CONSTRUCTION OF THE SCREENED |
| PORCH. SPECIFY ALL COLUMNS, BEAMS, STRUCTURAL |
| CONNECTORS TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301. |
| |
| 10 - ARCHITECT TO PROVIDE COMPLETE FRAMING DETAILS AND |
| SPECIFICATIONS FOR THE CONVERSION OF PORCH TO NEW |
| BATHROOM. SPECIFY FOOTINGS, PROVIDE COMPLETE FRAMING |
| DETAILS AND SPECIFICATIONS TO VERIFY COMPLIANCE WITH |
| THE DESIGN PRESSURES OF SEC. R301. SPECIFY ALL |
| STRUCTURAL CONNECTORS. PROVIDE COMPLETE WALL SECTION |
| PROVIDING ALL THE SPECIFICATIONS TO INTERIOR AND |
| EXTERIOR SIDE. |
| |
| 11- ARCHITECT TO PROVIDE IN ALL PLANS ALL THE |
| INFORMATION REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| ADMINISTRATIVE CODE AND CHAPTER 481 OF FLORIDA STATUTE. |
| MISSING THE FIRM LICENSE NUMBER, NAME OF ARCHITECT |
| SIGNING THE PLANS, LICENSE NUMBER OF ARCHITECT AND DATE |
| WHEN PLANS WERE SEALED. |
| |
| 12- PROVIDE ROOF FRAMING PLAN WITH COMPLETE |
| SPECIFICATIONS FOR NEW ROOF OVER THE PROPOSED PORCH. |
| SEE SEC. R803.2.3.1 FOR MIN. NAIL TYPE AND SPACING TO |
| BE USED FOR THE ROOF SHEATHING IN ALL ROOF ZONES. |
| |
| 13- SPECIFY SAFETY GLASS ON BATHROOM WINDOWS AS |
| REQUIRED BY SEC. R308.4. |
| |
| 14- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806. |
| |
| 15- SPECIFY ATTIC ACCESS SIZE AND LOCATION TO COMPLY |
| WITH SEC. R807. |
| |
| 16- REVISE ROOF PITCH SHOWN ON NORTH ELEVATION ON SHEET |
| A-2.1. |
| |
| 17- SPECIFY ALL DOORS AND WINDOWS TYPES AND SIZES. SEC. |
| 106.1.1 CITY AMENDMENTS TO FBC. |
| |
| 18- ENERGY CALCULATIONS SHOW CEILING FAN CREDIT. |
| SPECIFY ON PLANS CEILING FAN SIZE TO COMPLY WITH TABLE |
| C4.2.1.1 OF CHAPTER 11 OF 2007 FLORIDA RESIDENTIAL |
| CODE. |
| |
| 19- PROVIDE COMPLETE FRAMING DETAILS FOR THE |
| INSTALLATION THE THE BEDROOM FRENCH DOORS AND SLIDERS |
| AS SHOWN ON PLANS TO VERIFY COMPLIANCE WITH SEC. R301. |
| |
| 20- SHEET C-1.0: UPDATE CODE REFERENCED ON THE GENERAL |
| NOTES. CURRENT CODE IS THE 2007 FLORIDA RESIDENTIAL |
| CODE WITH 2009 REVISIONS. |
| |
| 21: ENERGY CALCULATIONS SUBMITTED: |
| A) REVISE FLOOR TYPE. THIS BUILDING DOESN'T HAVE A SLAB |
| ON GRADE. SEE PLANS. REVISE FRONT PAGE AND PAGE 2 OF 5. |
| |
| B) REVISE THE ROOF TYPE SHOWN ON SHEET 2 OF 5. SEE |
| PLANS. |
| |
| C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| |
| D) FILL ALL THE INFORMATION ON TOP OF THE FORM. |
| |