Plan Review Notes
Plan Review Notes For Permit 10120323
Permit Number 10120323
Review Stop M
Sequence Number 1
Notes
Date Text
2011-01-03 09:43:19PLAN DENIED
 OFFICE 127 HAS NO RETURN AIR ON THE PLANS. PLEASE
 PROVIDE RETURN PER SECTION 601.4 2007 FBC (M) BALANCED
 RETURN AIR.
 REFER TO SECTION 601.4 2007 FBC(M) FOR EXAM ROOMS 110
 THROUGH 116 AND 116 .
 PLEASE PROVIDE THE SIZE AND SPACING OF THE WEDGE
 ANCHORS ON THE DETAIL FOR CURB TO ROOF TIE DOWN.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  