Plan Review Notes For Permit 10120323 |
Permit Number |
10120323 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-01-03 09:43:19 | PLAN DENIED | | OFFICE 127 HAS NO RETURN AIR ON THE PLANS. PLEASE | | PROVIDE RETURN PER SECTION 601.4 2007 FBC (M) BALANCED | | RETURN AIR. | | REFER TO SECTION 601.4 2007 FBC(M) FOR EXAM ROOMS 110 | | THROUGH 116 AND 116 . | | PLEASE PROVIDE THE SIZE AND SPACING OF THE WEDGE | | ANCHORS ON THE DETAIL FOR CURB TO ROOF TIE DOWN. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | |
|