Plan Review Notes For Permit 10120293 |
Permit Number |
10120293 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-12-21 12:42:13 | 2240 PALM BEACH LAKES BOULEVARD, SUITE 302 | | PERMIT #10120293 | | REVIEW COMMENTS - FIRE | | | | | | DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION | | CODE 2007 EDITION. | | | | NEW OR EXISTING LIFE SAFETY EQUIPMENT (FIRE ALARM, FIRE | | SPRINKLERS, PORTABLE FIRE EXTINGUISHERS) NOT SHOWN ON | | PLANS FOR ANY OF THE OFFICE SPACES. | | | | SECTION 708 OF THE FLORIDA BUILDING CODE REQUIRES A | | 1-HOUR FIRE RATED PARTITION BETWEEN INDIVIDUAL TENANT | | SPACES EXCEPT FOR BUSINESS OCCUPANCIES, PROVIDED NO | | AREA BETWEEN FIRE-RATED PARTITIONS EXCEEDS 3,000 SQUARE | | FEET. THE NEW WALLS RESULT IN FIVE SEPARATE TENANT | | SPACES. PLEASE INDICATE WHICH EXISTING WALLS HAVE A | | FIRE RATING. | | | | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | FIRE/SMOKE BARRIER???PROTECT ALL OPENINGS. CHARACTERS | | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN | | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 | | FEET ON CENTER. (REFERENCE: SECTION 8.3.2.4 OF FLORIDA | | FIRE PREVENTION CODE ??? NFPA 101) | | | | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL | | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. | | (REFERENCE: SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION | | CODE ??? NFPA 101) | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|