2011-01-03 14:30:53 | BUILDING PLAN REVIEW |
| PERMIT: 10120293 |
| ADD: 2240 P B LAKES #302 |
| CONT: TYDAN CONSTRUCTION |
| TEL: (561)339-3717 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| 01/03/2011 |
| 1ST REVIEW: SPOKE WITH ARCHITECT STEVE YECKES ANSWERED |
| CONCERNS: |
| ACTION: PROVISO |
| |
| 1) PLEASE INDICATE COMPLIANCE WITH: FBC-B 712.6 FIRE |
| WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS |
| AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE |
| PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY |
| IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER |
| ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH |
| IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING |
| AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND |
| SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL |
| OPENINGS." |
| |
| 2) PROVIDE COMPLIANCE WITH: FBC-B 712.3 |
| FIRE-RESISTANCE-RATED WALLS. PENETRATIONS INTO OR |
| THROUGH FIRE WALLS, FIRE-BARRIER WALLS, SMOKE-BARRIER |
| WALLS AND FIRE PARTITIONS SHALL COMPLY WITH SECTIONS |
| 712.3.1 THROUGH 712.3.4. |
| |
| 3) DISSPROPORTIONATE COST REQUIRES 20% ABOVE CONTRACT |
| VALUE (11-4.1.6(2)(1)(2)(A) CHOOSING WHICH ELEMENTS TO |
| PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| THAT PROVIDE THE GREATEST ACCESS IN THE FOLLOWING |
| ORDER(I) AN ACCESSIBLE ENTRANCE. |
| THE NEW EXIT DOOR SHEET A-1 IS MISSING THE REQUIRED 18 |
| INCHES LATCH SIDE OF INSWING DOOR, FBC-B 11-4.13.6. |
| JAMES A. WITMER |
| TEL: (561)805-6715 |
| FAX:(561)805-6731 |
| E-MAIL: [email protected] |
2010-12-27 14:34:30 | BUILDING PLAN REVIEW |
| PERMIT: 10120293 |
| ADD: 2240 P B LAKES #302 |
| CONT: TYDAN CONSTRUCTION |
| TEL: (561)339-3717 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) ADDITIONAL INFORMATION IS REQUIRED. IT APPEARS THERE |
| MAY BE EITHER 3 OR 4 TENANTS WITHIN THE 3RD FLOOR, THE |
| PLANS DO INDICATE UP TO 14 OFFICES ON THIS FLOOR, |
| TENANT SEPERATION WALLS ARE NOT CLEARLY DEFINED. 2007 |
| FBC-B 708.1 EXCEPTION #1 DOES ALLOW FOR TENAT |
| SEPERATION WALLS NOT REQUIRING A 1-HOUR FIRE |
| -RESISTANCE WHEN THEY DO NOT EXCEED 3,000 SQ FT. |
| |
| 2) SHEET A-1 OFFICE SPACE 1 AND OFFICE SPACE 2 |
| INDICATES A NEW DOOR OPENING BEING CUT INTO THIS WALL, |
| THE COMMON WALL TO CONFERENCE ROOM #1 AND KITCHEN #2. |
| IS THIS A COMMUNICATING DOOR WITHIN A SINGLE TENANT OR |
| A COMMUNICATING DOOR BETWEEN |
| TWO SEPERATE TENANTS? AGAIN PROVIDE SQUARE FOOTAGE TO |
| SEE IF FBC-B 708.1 EXCEPTION #1 IS ALLOWED IN THIS |
| INSTANCE. BOTH THE PERMIT APPLICATION AND PLAN SHOULD |
| INCLUDE THIS WORK TO BE WITHIN THE DESCRIPTION OF WORK |
| TO BE COMPLETED UNDER THIS PERMIT. |
| |
| 3) PLEASE INDICATE COMPLIANCE WITH: FBC-B 712.6 FIRE |
| WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS |
| AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE |
| PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY |
| IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER |
| ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH |
| IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING |
| AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND |
| SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL |
| OPENINGS." |
| |
| 4) PROVIDE COMPLIANCE WITH: FBC-B 712.3 |
| FIRE-RESISTANCE-RATED WALLS. PENETRATIONS INTO OR |
| THROUGH FIRE WALLS, FIRE-BARRIER WALLS, SMOKE-BARRIER |
| WALLS AND FIRE PARTITIONS SHALL COMPLY WITH SECTIONS |
| 712.3.1 THROUGH 712.3.4. |
| |
| 5) THE NEW EXIT DOOR SHEET A-1 IS MISSING THE REQUIRED |
| 18 INCHES LATCH SIDE OF INSWING DOOR, FBC-B 11-4.13.6. |
| |
| JAMES A. WITMER |