Plan Review Notes
Plan Review Notes For Permit 10120179
Permit Number 10120179
Review Stop B
Sequence Number 3
Notes
Date Text
2011-01-20 13:04:10****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****CONTRACTOR TO PROVIDE REVISED FLOOR PLAN/REVISED
 DESIGN PRESSURES AT INSPECTION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 REVISE PLAN TO SHOW COMPLIANCE WITH THE FOLLOWING:
  
 1. PROVIDE BUILDING HEIGHT. DESIGN PRESSURES FOR
 BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED USING
 ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002. BUILDING HEIGHT IS REQUIRED
 TO DETERMINE DESIGN PRESSURES.
  
 REVISE PLAN TO SHOW BUILDING HEIGHT. BASED ON
 CONTRACTOR'S RESUBMITTAL FORM, BUILDING HEIGHT IS 40
 FEET. PER TELEPHONE CONVERSATION, ALL OPENINGS ARE IN
 ZONE 4.
  
 PER ASCE7-05, +49.46/-56.91 REQUIRED