Plan Review Notes For Permit 10120179 |
Permit Number |
10120179 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2011-01-20 13:04:10 | ****PROVISO**** | | ****ISSUED AT CONTRACTOR'S RISK**** | | ****CONTRACTOR TO PROVIDE REVISED FLOOR PLAN/REVISED | | DESIGN PRESSURES AT INSPECTION**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2007 | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | REVISE PLAN TO SHOW COMPLIANCE WITH THE FOLLOWING: | | | | 1. PROVIDE BUILDING HEIGHT. DESIGN PRESSURES FOR | | BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED USING | | ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN ENGINEER | | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED | | ORIGINALS FAC61G15-23.002. BUILDING HEIGHT IS REQUIRED | | TO DETERMINE DESIGN PRESSURES. | | | | REVISE PLAN TO SHOW BUILDING HEIGHT. BASED ON | | CONTRACTOR'S RESUBMITTAL FORM, BUILDING HEIGHT IS 40 | | FEET. PER TELEPHONE CONVERSATION, ALL OPENINGS ARE IN | | ZONE 4. | | | | PER ASCE7-05, +49.46/-56.91 REQUIRED |
|