 REVIEW COMMENTS - FIRE
  
  
 DOORS THAT OPEN (EXISTING ENTRANCE DOORS) ONTO EXIT
 ACCESS CORRIDORS SHALL HAVE NOT LESS THAN A 20-MINUTE
 FIRE PROTECTION RATING AND SHALL BE SELF-CLOSING AND
 SELF-LATCHING.
  
 REMOVE NON-FUNCTIONING ENTRANCE DOOR (UNIT 2502) TO
 AVOID CONFUSION FOR EMERGENCY RESPONDERS TRYING TO GAIN
 ACCESS TO THE UNIT.
  
 THE HARD-WIRED SMOKE ALARMS SHALL SOUND ONLY WITHIN THE
 DWELLING UNIT; SMOKE ALARMS SHALL NOT BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM.
  