2010-12-17 11:50:32 | 5200 NORTH FLAGLER DRIVE, #2502 & #2503 | | PERMIT #10120173 | | REVIEW COMMENTS - FIRE | | | | | | DOORS THAT OPEN (EXISTING ENTRANCE DOORS) ONTO EXIT | | ACCESS CORRIDORS SHALL HAVE NOT LESS THAN A 20-MINUTE | | FIRE PROTECTION RATING AND SHALL BE SELF-CLOSING AND | | SELF-LATCHING. | | | | REMOVE NON-FUNCTIONING ENTRANCE DOOR (UNIT 2502) TO | | AVOID CONFUSION FOR EMERGENCY RESPONDERS TRYING TO GAIN | | ACCESS TO THE UNIT. | | | | THE HARD-WIRED SMOKE ALARMS SHALL SOUND ONLY WITHIN THE | | DWELLING UNIT; SMOKE ALARMS SHALL NOT BE TIED INTO THE | | BUILDING FIRE ALARM SYSTEM. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | (561) 805-6730 | | |
|