2010-12-14 08:57:19BUILDING PLAN REVIEW
 PERMIT: 10120173
 ADD: 5200 N FLAGLER #2502& 2503
 CONT: A&A DEVELOPMENT GROUP LLC
 TEL: (561)719-0895
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 (CONDOMINIUM SUITES) WHICH COMBINE TO FORM 'THE SITE'.
 A 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF OF
 TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
  
 2) MASTER BATH SHOWER TENANT SEPERATION WALLS. FBC-B
 1207.2 AIR BORNE SOUND REQUIREMENTS.
  
 3) THIS IS ONLY IF ADDITIONAL FLOORING IS TO BE
 APPLIED. FBC-B 1207.3 STRUCTURE BORNE SOUND
 REQUIREMENTS, MUST MEET THE SOUND INSULATION OF 50 STC.
  
 4) MASTER BATH SHOWER TO MEET THE REQUIREMENTS OF FBC-B
 2509.2 BASE FOR TILE: SHOWER, EITHER CEMENT,
 FIBER-CEMENT, OR GLASS MAT GYPSUM AS A BACKING BOARD.
  
 JIM WITMER C. B. O.