Plan Review Notes For Permit 10120071 |
Permit Number |
10120071 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-12-21 14:14:31 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW | | COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE | | INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS. | | THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL. | | | | 2. PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT | | FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER | | (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO | | HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT | | WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE | | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT | | BE NOTARIZED. | | | | 3. FBC3501.3.5, PROVIDE DOCUMENTATION TO SHOW THAT THE | | FABRIC MEETS THE REQUIREMENT OF NFPA701. | | | | 4. PROVIDE DISTANCE FROM GRADE TO BOTTOM OF AWNING, SEE | | FBC3105.1. | | | | 5. REVISE SITE PLAN TO SHOW PROPOSED AWNING LOCATION. | | | | 6. SEE FBC3105.4, PLAN INCORRECTLY STATES THAT FABRIC | | TO BE REMOVED AT 75MPH SUSTAINED 90MPH 3 SECOND GUST. | | PLEASE SEE FBC3105.4 FOR DESIGN CRITERIA. | | | | |
|