2011-03-21 08:24:12****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE TO EXPOSURE C OR PROVIDE CALCULATIONS FOR
 TRANSITION ZONE PER ASCE7-05.
  
 2. ROOF TILE FASTENING SPECIFICATION REQUIRED WITH
 SEPARATE ROOF PERMIT (NOA 10-0706.07 REVIEWED BY DOR &
 SUBMITTED).
  
 3. DESIGN CRITERIA TO BE REVISED TO PARTIALLY ENCLOSED.
  
 4. SPECIFY VENTILATION ATTIC VENTILATION FBC R806.
  
 5. FBC R807, ATTIC ACCESS REQUIRED.
  
  