Plan Review Notes
Plan Review Notes For Permit 10120061
Permit Number 10120061
Review Stop B
Sequence Number 2
Notes
Date Text
2011-03-17 15:22:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. 4. REVISE EXPOSURE CATEGORY OR PROVIDE CALCULATIONS
 FOR EXPOSURE B DESIGN PRESSURES. FBC1609, FBC
 R301.2.1.4. NOTE THAT THE CODE CHANGED EFFECTIVE MARCH
 1, 2009.
  
 2ND REVIEW, NOT ADDRESSED. REVISE TO EXPOSURE C OR
 PROVIDE CALCULATIONS FOR TRANSITION ZONE PER ASCE7-05.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, ROOF TILE. ON THE PRODUCT APPROVAL, INDICATE
 METHOD OF FASTENING SO THAT COMPLIANCE WITH WIND DESIGN
 CRITERIA CAN BE DETERMINED. IF FOAM ADHESIVE IS USED,
 PROVIDE PRODUCT APPROVAL FOR THE ADHESIVE. PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL.
  
 2ND REVIEW, PRODUCT APPROVAL PROVIDED, METHOD OF
 ATTACHMENT NOT SPECIFIED. IF NOT PROVIDED PRIOR TO
 ISSUANCE, THIS WILL BE REQUIRED WITH THE ROOF PERMIT
 APPLICATION.
  
 3-4. ADDRESSED.
  
 5. SEE DEFINITION OF PARTIALLY ENCLOSED, ASCE7-05, AND
 EXPLAIN RATIONALE FOR DESIGNING THIS STRUCTURE TO
 PARTIALLY ENCLOSED DESIGN PRESSURES. IT APPEARS THAT
 THE PROPOSED IMPROVEMENT IS NOT A FREE STANDING
 STRUCTURE, BUT AN ADDITION TO AN EXISTING STRUCTURE.
  
 2ND REVIEW, THIS HAS BEEN REVISED TO OPEN. PLEASE SEE
 DEFINITIONS IN ASCE7-05 AND REVISE.
  
 PROVISO ITEMS:
  
 FBC R806, VENTILATION SHOWN GRAPHICALLY, AREA TO COMPLY
 WITH FBC R806.
  
 FBC R807, ATTIC ACCESS REQUIRED.
  
 THIS PERMIT CAN BE ISSUED AT RISK WITH PROVISO FOR A
 REVISION UPON REQUEST.
  
  
  
  
  