2011-03-17 15:22:59 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| 1. 4. REVISE EXPOSURE CATEGORY OR PROVIDE CALCULATIONS |
| FOR EXPOSURE B DESIGN PRESSURES. FBC1609, FBC |
| R301.2.1.4. NOTE THAT THE CODE CHANGED EFFECTIVE MARCH |
| 1, 2009. |
| |
| 2ND REVIEW, NOT ADDRESSED. REVISE TO EXPOSURE C OR |
| PROVIDE CALCULATIONS FOR TRANSITION ZONE PER ASCE7-05. |
| |
| 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| FAC9B72, ROOF TILE. ON THE PRODUCT APPROVAL, INDICATE |
| METHOD OF FASTENING SO THAT COMPLIANCE WITH WIND DESIGN |
| CRITERIA CAN BE DETERMINED. IF FOAM ADHESIVE IS USED, |
| PROVIDE PRODUCT APPROVAL FOR THE ADHESIVE. PRODUCT |
| APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL. |
| |
| 2ND REVIEW, PRODUCT APPROVAL PROVIDED, METHOD OF |
| ATTACHMENT NOT SPECIFIED. IF NOT PROVIDED PRIOR TO |
| ISSUANCE, THIS WILL BE REQUIRED WITH THE ROOF PERMIT |
| APPLICATION. |
| |
| 3-4. ADDRESSED. |
| |
| 5. SEE DEFINITION OF PARTIALLY ENCLOSED, ASCE7-05, AND |
| EXPLAIN RATIONALE FOR DESIGNING THIS STRUCTURE TO |
| PARTIALLY ENCLOSED DESIGN PRESSURES. IT APPEARS THAT |
| THE PROPOSED IMPROVEMENT IS NOT A FREE STANDING |
| STRUCTURE, BUT AN ADDITION TO AN EXISTING STRUCTURE. |
| |
| 2ND REVIEW, THIS HAS BEEN REVISED TO OPEN. PLEASE SEE |
| DEFINITIONS IN ASCE7-05 AND REVISE. |
| |
| PROVISO ITEMS: |
| |
| FBC R806, VENTILATION SHOWN GRAPHICALLY, AREA TO COMPLY |
| WITH FBC R806. |
| |
| FBC R807, ATTIC ACCESS REQUIRED. |
| |
| THIS PERMIT CAN BE ISSUED AT RISK WITH PROVISO FOR A |
| REVISION UPON REQUEST. |
| |
| |
| |
| |
| |