2010-12-29 15:56:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. 4. REVISE EXPOSURE CATEGORY OR PROVIDE CALCULATIONS
 FOR EXPOSURE B DESIGN PRESSURES. FBC1609, FBC
 R301.2.1.4. NOTE THAT THE CODE CHANGED EFFECTIVE MARCH
 1, 2009.
  
 R301.2.1.4 EXPOSURE CATEGORY. FOR EACH WIND DIRECTION
 CONSIDERED, AN EXPOSURE CATEGORY THAT ADEQUATELY
 REFLECTS THE CHARACTERISTICS OF GROUND SURFACE
 IRREGULARITIES SHALL BE DETERMINED FOR THE SITE AT
 WHICH THE BUILDING OR STRUCTURE IS TO BE CONSTRUCTED.
 FOR A SITE LOCATED IN THE TRANSITION ZONE BETWEEN
 CATEGORIES, THE CATEGORY RESULTING IN THE LARGEST WIND
 FORCES SHALL APPLY. ACCOUNT SHALL BE TAKEN OF
 VARIATIONS IN GROUND SURFACE ROUGHNESS THAT ARISE FROM
 NATURAL TOPOGRAPHY AND VEGETATION AS WELL AS FROM
 CONSTRUCTED FEATURES. FOR ANY GIVEN WIND DIRECTION, THE
 EXPOSURE IN WHICH A SPECIFIC BUILDING OR OTHER
 STRUCTURE IS SITED SHALL BE ASSESSED AS BEING ONE OF
 THE FOLLOWING CATEGORIES:
  
 EXCEPTION: AN INTERMEDIATE EXPOSURE BETWEEN THE
 EXPOSURE CATEGORIES DEFINED IS PERMITTED IN A
 TRANSITION ZONE PROVIDED THAT IT IS DETERMINED BY A
 RATIONAL ANALYSIS METHOD.
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, ROOF TILE. ON THE PRODUCT APPROVAL, INDICATE
 METHOD OF FASTENING SO THAT COMPLIANCE WITH WIND DESIGN
 CRITERIA CAN BE DETERMINED. IF FOAM ADHESIVE IS USED,
 PROVIDE PRODUCT APPROVAL FOR THE ADHESIVE. PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL.
  
 3. PRODUCT APPROVAL FOR A BUR ROOF WAS PROVIDED, PLANS
 SHOW A TILE ROOF. PLEASE ADDRESS.
  
 3. TERMITE PROTECTION REQUIRED FBC R 320.
  
 4. TRUSS DESIGN ENGINEERING DOCUMENTS REQUIRED WITH ALL
 INFORMATION REQUIRED BY FBC R802.1.6.1. TRUSS
 ENGINEERING TO BE REVIEWED BY DESIGNER OF RECORD PRIOR
 TO SUBMITTAL.
  
 5. SEE DEFINITION OF PARTIALLY ENCLOSED, ASCE7-05, AND
 EXPLAIN RATIONALE FOR DESIGNING THIS STRUCTURE TO
 PARTIALLY ENCLOSED DESIGN PRESSURES. IT APPEARS THAT
 THE PROPOSED IMPROVEMENT IS NOT A FREE STANDING
 STRUCTURE, BUT AN ADDITION TO AN EXISTING STRUCTURE.
  
  
  
  
  
  