Date Text
2010-12-03 16:57:17801 SOUTH OLIVE AVENUE, UNIT #706
 PERMIT #10120033
 MASTER #10080601
 REVIEW COMMENTS - FIRE
  
 A HIGH-RISE APARTMENT BUILDING EXISTS AT THIS ADDRESS;
 THEREFORE, THE SYSTEM MUST BE DESIGNED ACCORDING TO
 NFPA 13. SEVERAL GENERAL NOTES MAKE REFERENCE TO NFPA
 13R WHICH IS APPLICABLE ONLY TO RESIDENTIAL OCCUPANCIES
 UP TO (AND INCLUDING) FOUR STORIES IN HEIGHT.
  
 SPRINKLER PROTECTION IS REQUIRED IN CLOSESTS AND
 PANTRIES PER NFPA 13 SECTION 8.14.8.2 (2002 EDITION).
 SPRINKLERS ARE NOT REQUIRED IN THESE SPACES IF THE
 DWELLING UNIT IS LOCATED WITHIN A HOTEL OR MOTEL.
  
 PROVIDE HYDRAULIC CALCULATIONS FOR THE FOUR MOST
 DEMANDING SPRINKLERS PER NFPA 13 SECTION 11.2.3.5.
  
 THE THREE NEW RESIDENTIAL SIDEWALL SPRINKLERS SUPPLIED
 BY THE BRANCH LINE DO NOT APPEAR TO BE CONNECTED TO THE
 REST OF THE SYSTEM.
  
 SPRINKLER PROTECTION IS REQUIRED BELOW SOFFITS GREATER
 THAN 8-INCHES IN WIDTH WHEN SIDEWALL SPRINKLERS ARE
 LOCATED IN THAT SOFFIT PER NFPA 13 SECTION 8.7.4.1.3.2.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW