2010-12-20 10:10:50FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. A RESTROOM WILL BE REQUIRED ON THE 3RD FLOOR TO BE
 WITHIN ONE STORY LEVEL.
 PLUMBING 403.4.1 LOCATION OF TOILET FACILITIES IN
 OCCUPANCIES OTHER THAN COVERED MALLS. IN OCCUPANCIES
 OTHER THAN COVERED MALLS, THE REQUIRED PUBLIC AND
 EMPLOYEE TOILET FACILITIES SHALL BE LOCATED NOT MORE
 THAN ONE STORY ABOVE OR BELOW THE SPACE REQUIRED TO BE
 PROVIDED WITH TOILET FACILITIES, AND THE PATH OF TRAVEL
 TO SUCH FACILITIES SHALL NOT EXCEED A DISTANCE OF 500
 FEET (152 M).
  
 2. DRINKING FOUNTIANS ARE REQUIRED IN BUSINESS
 OCCUPANIES.
 TABLE 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING
 FIXTURES
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR