Plan Review Notes For Permit 10120017 |
Permit Number |
10120017 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-12-20 10:10:50 | FBC PLUMBING 2007 REVIEW #1 | | DENIED: | | | | 1. A RESTROOM WILL BE REQUIRED ON THE 3RD FLOOR TO BE | | WITHIN ONE STORY LEVEL. | | PLUMBING 403.4.1 LOCATION OF TOILET FACILITIES IN | | OCCUPANCIES OTHER THAN COVERED MALLS. IN OCCUPANCIES | | OTHER THAN COVERED MALLS, THE REQUIRED PUBLIC AND | | EMPLOYEE TOILET FACILITIES SHALL BE LOCATED NOT MORE | | THAN ONE STORY ABOVE OR BELOW THE SPACE REQUIRED TO BE | | PROVIDED WITH TOILET FACILITIES, AND THE PATH OF TRAVEL | | TO SUCH FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 | | FEET (152 M). | | | | 2. DRINKING FOUNTIANS ARE REQUIRED IN BUSINESS | | OCCUPANIES. | | TABLE 403.1 MINIMUM NUMBER OF REQUIRED PLUMBING | | FIXTURES | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | | | | | | | |
|