Plan Review Notes For Permit 10120017 |
Permit Number |
10120017 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-12-06 12:57:16 | 1000 OLD OKEECHOBEE ROAD | | PERMIT NUMBER 10120017 | | COMMERCIAL RENOVATION | | PRIOR TO BEING USED BY THE FLORIDA DEPARTMENT OF | | TRANSPORTATION IT WAS USED BY THE CITY OF WEST PALM | | BEACH FIRE RESCUE DEPARTMENT TO TRAIN ITS PROFESSIONAL | | FIREFIGHTERS AND PARAMEDICS | | | | | | 1. BUILDING ADDRESS IS REQUIRED. A MINIMUM OF AT LEAST | | 6" HIGH AND AT LEAST 1" WIDE NUMBERS ARE REQUIRED. | | | | 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | 3. ALL STAIRWELL DOORS ARE TO BE AT LEAST 90 MINUTE | | FIRE RATED DOORS EQUIPPED WITH SELF-CLOSING DEVICES. | | | | 4. PORTABLE FIRE EXTINGUISHERS ARE REQUIRED WHEREBY | | TRAVEL DISTANCE DOES NOT EXCEED 75 FEET OF TRAVEL | | DISTANCE. | | | | 5. THE CITY OF WEST PALM BEACH CONSTRUCTION SERVICES | | DEPARTMENT IS LOCATED AT 401 CLEMATIS STREET NOT | | 200-2ND STREET | | | | 6. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | WITH NFPA 241. | | | | 7. DEBRIS SHALL BE REMOVED FROM THE BUILDING DAILY. | | | | 8. SUITABLE ACCESS IS TO BE PROVIDED FOR FIRE AND | | PARAMEDICAL EQUIPMENT. | | | | | | APPROVED PROVISO | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | (561) 804-4724 PHONE | | (561) 804-4774 FAX |
|