2010-12-20 13:17:27 | BUILDING PLAN REVIEW |
| PERMIT:10120017 |
| ADD: 900 N FLORIDA MANGO/ AKA1000 OKEECHOBEE RD |
| CONT: NELCO DIVERSIFIED INC/ NELCO CONSTRUCTION |
| TEL: (813)477-0574 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) COVERSHEET: |
| |
| 1A) PLEASE REVIEW TYPE OF OCCUPANCY, THE PLANS INDICATE |
| A BUSSINESS OCCUPANCY WHERE AS APPROXIMATELY ONLY 50% |
| OF THE FLOOR AREA IS CONSIDERED A BUSINESS OCCUPANCY. |
| THE 3RD AND 4TH FLOORS ARE INDICATED TO BE STORAGE |
| PLEASE INDICATE IF THE STORAGE OCCUPANCY IS TO BE A S-1 |
| OR S-2 OCCUPANCY. PLEASE NOTE THAT TABLE 503 LIMITS THE |
| HEIGHT OF A TYPE IIB BUILDING TO THREE STORIES. THIS |
| BUILDING TO BE CONSIDERED A MIXED USE OCCUPANCY, FBC-B |
| 508.3. |
| |
| 1B) PLEASE REVIEW THE OCCUPANT LOADS FOR BUSINESS 2ND |
| FLOOR @ 100 SQ FT & STORAGE OCCUPANCY @ 300 SQ FT THIS |
| WILL EFFECT THE PROPOSED OCCUPANT LOADS FBC-B TABLE |
| 1004.1.1. |
| |
| 1C) COVER SHEET MEANS OF EGRESS ANALYSIS IS INDICATED |
| AS FBC-B SECTION 1015.1, PLEASE ALSO CONSIDER FBC-B |
| TABLE 1019.2 |
| BUILDINGS WITH ONE EXIT PLEASE REVIEW STORAGE 1 STORY & |
| 100 FT TRAVEL DISTANCE. |
| |
| 2) SHEET A-1: |
| |
| 2A) THIS IS A FOUR STORY BUILDING AND VERTICAL EXIT |
| WHICH REQUIRES A 2 HOUR RATED WALL AND 1 1/2 HOUR |
| OPENING PROTECTIVE. NOTE 19 DOES NOT PROVIDE ANY RATING |
| FOR THIS DOOR PLEASE REVIEW FBC-B TABLE 715.4, AND |
| PROVIDE FIRE RATING APPROVALS FOR DOORS. |
| |
| 2B) THE SECOND FLOOR BEING A BUSINESS OCCUPANCY AND AN |
| OCCUPANT LOAD GREATER THAN 5 (500 SQ FT) PLEASE PROVIDE |
| COMPLIANCE WITH FBC-B 11-4.1.6(1)(K)(III) VERTICAL |
| ACCESSIBILITY. |
| |
| 3) PRODUCT APPROVALS: |
| |
| 3A) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 3B) FLEMING DOOR FL3341-R2 IT APPEARS THAT THIS DOOR |
| DOES NOT MEET THE PRESSURES FOR THE DOOR LEADING ONTO |
| THE ROOF, NOR THE EXIT DOOR FROM THE VERTICAL EXIT |
| STAIR LOCATED IN A END ZONE. |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| |
| |