2010-12-20 13:17:27BUILDING PLAN REVIEW
 PERMIT:10120017
 ADD: 900 N FLORIDA MANGO/ AKA1000 OKEECHOBEE RD
 CONT: NELCO DIVERSIFIED INC/ NELCO CONSTRUCTION
 TEL: (813)477-0574
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COVERSHEET:
  
 1A) PLEASE REVIEW TYPE OF OCCUPANCY, THE PLANS INDICATE
 A BUSSINESS OCCUPANCY WHERE AS APPROXIMATELY ONLY 50%
 OF THE FLOOR AREA IS CONSIDERED A BUSINESS OCCUPANCY.
 THE 3RD AND 4TH FLOORS ARE INDICATED TO BE STORAGE
 PLEASE INDICATE IF THE STORAGE OCCUPANCY IS TO BE A S-1
 OR S-2 OCCUPANCY. PLEASE NOTE THAT TABLE 503 LIMITS THE
 HEIGHT OF A TYPE IIB BUILDING TO THREE STORIES. THIS
 BUILDING TO BE CONSIDERED A MIXED USE OCCUPANCY, FBC-B
 508.3.
  
 1B) PLEASE REVIEW THE OCCUPANT LOADS FOR BUSINESS 2ND
 FLOOR @ 100 SQ FT & STORAGE OCCUPANCY @ 300 SQ FT THIS
 WILL EFFECT THE PROPOSED OCCUPANT LOADS FBC-B TABLE
 1004.1.1.
  
 1C) COVER SHEET MEANS OF EGRESS ANALYSIS IS INDICATED
 AS FBC-B SECTION 1015.1, PLEASE ALSO CONSIDER FBC-B
 TABLE 1019.2
 BUILDINGS WITH ONE EXIT PLEASE REVIEW STORAGE 1 STORY &
 100 FT TRAVEL DISTANCE.
  
 2) SHEET A-1:
  
 2A) THIS IS A FOUR STORY BUILDING AND VERTICAL EXIT
 WHICH REQUIRES A 2 HOUR RATED WALL AND 1 1/2 HOUR
 OPENING PROTECTIVE. NOTE 19 DOES NOT PROVIDE ANY RATING
 FOR THIS DOOR PLEASE REVIEW FBC-B TABLE 715.4, AND
 PROVIDE FIRE RATING APPROVALS FOR DOORS.
  
 2B) THE SECOND FLOOR BEING A BUSINESS OCCUPANCY AND AN
 OCCUPANT LOAD GREATER THAN 5 (500 SQ FT) PLEASE PROVIDE
 COMPLIANCE WITH FBC-B 11-4.1.6(1)(K)(III) VERTICAL
 ACCESSIBILITY.
  
 3) PRODUCT APPROVALS:
  
 3A) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3B) FLEMING DOOR FL3341-R2 IT APPEARS THAT THIS DOOR
 DOES NOT MEET THE PRESSURES FOR THE DOOR LEADING ONTO
 THE ROOF, NOR THE EXIT DOOR FROM THE VERTICAL EXIT
 STAIR LOCATED IN A END ZONE.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
  
  