2011-01-28 10:41:46BUILDING PLAN REVIEW
 PERMIT:10110685
 ADD: 410 EVERNIA ST
 CONT:BESSENROTH BUILDERS INC/ CBC1255316
 TEL: (561)324-4871
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THERE ARE NO ARCHITECTURAL PLANS SUBMITTED
 INDICATING SLAB CUT AND REPAIR FOR PLUMBING WASTE PIPES
 NOR HOW VENT LINES TO BE INSTALLED.
  
 2) THE PLANS FAIL TO PROVIDE VERTICAL ACCESSIBILITY TO
 THE MEZZANINE LEVEL, THIS BUILDING WAS ORIGINALLY
 DESIGNED AS RESIDENTIAL NOT REQUIRING
 VERTICAL ACCESSIBILITY. 11-4.1.6(1)(K)(III).
  
 3) THE CURERNT CONTRACTOR BESSENROTH BUILDERS/
 CBC1255316 WILL BE WORKING BEYOND THEIR SCOPE OF
 LICENSURE. FL S 489.105(B)
 BUILDING CONTRACTOR??? MEANS A CONTRACTOR WHOSE
 SERVICES ARE LIMITED TO CONSTRUCTION OF COMMERCIAL
 BUILDINGS AND SINGLE-DWELLING OR MULTIPLE-DWELLING
 RESIDENTIAL BUILDINGS, WHICH COMMERCIAL OR RESIDENTIAL
 BUILDINGS DO NOT EXCEED THREE STORIES IN HEIGHT, AND
 ACCESSORY USE STRUCTURES IN CONNECTION THEREWITH OR A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO REMODELING,
 REPAIR, OR IMPROVEMENT OF ANY SIZE BUILDING IF THE
 SERVICES "DO NOT AFFECT THE STRUCTURAL MEMBERS OF THE
 BUILDING." WE BELIEVE THAT CUTTING THE FIRST FLOOR SLAB
 AND CORE BORING THE MEZZANINE FLOOR SLAB WOULD BE
 AFFECTING STRUCTURAL MEMBERS.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  