2010-12-16 16:53:30410 EVERNIA STREET SUITE#117
 PERMIT #10110685
 REVIEW COMMENTS - FIRE
  
 PERMIT APPLICATION SHOWS SUITE NUMBER 117; SUBMITTED
 PLANS REFER TO LOFT NUMBER 5. PLEASE CLARIFY THE
 CORRECT SUITE OR LOFT ASSOCIATED WITH THIS PROJECT.
  
 IS THIS A CHANGE OF USE OR OCCUPANCY FOR THIS SUITE?
 FLOOR PLANS DO NOT LABEL THE NAMES OR USE OF EACH ROOM.
 NO ARCHITECTURAL PLANS PROVIDED.
  
 THE EXISTING RESIDENTIAL FIRE SPRINKLERS NEED TO BE
 REPLACED WITH COMMERCIAL STYLE FIRE SPRINKLERS.
 SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE SPRINKLER
 WORK.
  
 PROVIDE COMMERCIALLY TAGGED/CERTIFIED PORTABLE FIRE
 EXTINGUISHERS (2A:10BC MIIMUM).
  
 EXITING THROUGH A KITCHEN IS NOT PERMITTED BY THE
 FLORIDA FIRE PREVENTION CODE (NFPA 101 - LIFE SAFETY
 CODE).
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730