Plan Review Notes
Plan Review Notes For Permit 10110629
Permit Number 10110629
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-12-03 09:30:441610 PALM BEACH LAKES BOULEVARD
 PERMIT NUMBER 10110629
 "LOW VOLTAGE FOR KITCHEN ADDITION"
  
  
 1. PLEASE PROVIDE CUT SHEETS FOR FIRE ALARM DEVICES
 PLANNED TO BE INSTALLED AT THE LOCATION.
  
 2. PLEASE LABEL THE VARIOUS ROOMS DISPLAYED ON THE
 PLANS.
  
 3. PLEASE INDICATE INSTALLATION HEIGHTS FOR MANUAL PULL
 STATIONS AND HORN STROBES DISPLAYED ON THE PLANS.
  
 4. PLEASE ADD NOTES TO THE PLANS - THE FIRE ALARM
 INSTALLATION IS TO COMPLY WITH NFPA 72, THE NATIONAL
 FIRE ALARM CODE, SMOKE DETECTORS ARE TO BE INSTALLED A
 MINIMUM OF AT LEAST THREE FEET FROM AIR CONDITIONER
 DIFFUSERS, WHEN DUCT DETECTORS ARE ACTIVATED THEY ARE
 TO ACTIVATE A GENERAL ALARM AS PER LOCAL POLICY.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
  