Plan Review Notes For Permit 10110629 |
Permit Number |
10110629 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-12-03 09:30:44 | 1610 PALM BEACH LAKES BOULEVARD | | PERMIT NUMBER 10110629 | | "LOW VOLTAGE FOR KITCHEN ADDITION" | | | | | | 1. PLEASE PROVIDE CUT SHEETS FOR FIRE ALARM DEVICES | | PLANNED TO BE INSTALLED AT THE LOCATION. | | | | 2. PLEASE LABEL THE VARIOUS ROOMS DISPLAYED ON THE | | PLANS. | | | | 3. PLEASE INDICATE INSTALLATION HEIGHTS FOR MANUAL PULL | | STATIONS AND HORN STROBES DISPLAYED ON THE PLANS. | | | | 4. PLEASE ADD NOTES TO THE PLANS - THE FIRE ALARM | | INSTALLATION IS TO COMPLY WITH NFPA 72, THE NATIONAL | | FIRE ALARM CODE, SMOKE DETECTORS ARE TO BE INSTALLED A | | MINIMUM OF AT LEAST THREE FEET FROM AIR CONDITIONER | | DIFFUSERS, WHEN DUCT DETECTORS ARE ACTIVATED THEY ARE | | TO ACTIVATE A GENERAL ALARM AS PER LOCAL POLICY. | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | (561) 804-4724 PHONE | | (561) 804-4774 FAX | | |
|