2010-12-30 11:08:41 | | | BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC | | 210.12 | | PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94 | | THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2 | | TAMPER -RESISTANCE RECEPTACLES REQUIRED. NEC 406.11, | | 210.52 | | MAXIMUM MAIN BREAKER FOR A RESIDENTIAL SERVICE USING | | 2/0 COPPER CONDUCTORS IS 200 AMPERES. NEC TABLE 310.15 | | DEDICATED GENERAL PURPOSE GFCI RECEPTACLE REQUIRED IN | | THE LAUNDRY ROOM. NEC 210. | | EACH BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | CIRCUIT. NEC 210-11(C)(3) | | LAUNDRY AREA REQUIRES A RECEPTACLE NEC 210.52 (F) | | DRYER BRANCH CIRCUIT APPEARS UNDERSIZED. | | INSTA-HOT POWER USAGE INCORRECTLY LISTED. WIRE SIZES | | ARE INCORRECT. | | GFCI PROTECTED OUTLETS ARE REQUIRED FRONT AND BACK AT | | EACH RESIDENTIAL BUILDING AND AT THE LOCATION OF THE | | MECHANICAL EQUIPMENT . NEC 210-52 (E) (1), 210-63. | | INDICATE THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR | | AND ALL GROUNDING ELECTRODES FOR ALL BUILDINGS. NEC | | 250- 52 | | RECEPTACLE SPACING IN SEVERAL AREAS REQUIRES | | CORRECTION. NEC 210.52(A)(1) | | CARBON MONOXIDE DETECTORS REQUIRED. F.S. 553.885 | | ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718 | | | | |
|