Notes
Date Text
2010-12-30 11:06:12 
 BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC
 210.12
 PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94
 THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2
 TAMPER -RESISTANCE RECEPTACLES REQUIRED. NEC 406.11,
 210.52
 MAXIMUM MAIN BREAKER FOR A RESIDENTIAL SERVICE USING
 2/0 COPPER CONDUCTORS IS 200 AMPERES. NEC TABLE 310.15
 DEDICATED GENERAL PURPOSE GFCI RECEPTACLE REQUIRED IN
 THE LAUNDRY ROOM. NEC 210.
 EACH BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210-11(C)(3)
 LAUNDRY AREA REQUIRES A RECEPTACLE NEC 210.52 (F)
 DRYER BRANCH CIRCUIT APPEARS UNDERSIZED.
 INSTA-HOT POWER USAGE INCORRECTLY LISTED. WIRE SIZES
 ARE INCORRECT.
 GFCI PROTECTED OUTLETS ARE REQUIRED FRONT AND BACK AT
 EACH RESIDENTIAL BUILDING AND AT THE LOCATION OF THE
 MECHANICAL EQUIPMENT . NEC 210-52 (E) (1), 210-63.
 INDICATE THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR
 AND ALL GROUNDING ELECTRODES FOR ALL BUILDINGS. NEC
 250- 52
 RECEPTACLE SPACING IN SEVERAL AREAS REQUIRES
 CORRECTION. NEC 210.52(A)(1)
 CARBON MONOXIDE DETECTORS REQUIRED F.S. 553.885
  
 ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718
  