Plan Review Notes For Permit 10110409 |
Permit Number |
10110409 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-16 12:21:14 | DENIED BY BUILDING | | | | 1) ITEM NUMBER 4 OF THE PROPOSED WORK ON THE ESTIMATE | | SPECIFIES COPPER DRIP EDGE, FLASHING AND VENTS AND | | GALVANIZED HIP AND RIDGE CHANNEL, BREAK AND VALLEY | | METAL. RAS 111 SECTION 4 REQUIRES ROOF METALS TO BE | | COMPATIBLE IN ORDER TO MINIMIZE GALVANIC CORRISION. THE | | COPPER AND GALVANIZED STEEL ARE NOT COMPATIBLE. PLEASE | | SPECIFY HOW COMPLIANCE WITH THIS REQUIREMENT WILL BE | | MET. | | | | 2) SPECIFY THE SLOPE OF THE PITCHED ROOF. | | | | 3) SPECIFY THE SQUARE FEET OF THE FLAT ROOF AND OF THE | | SLOPED ROOF. | | | | 4) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|