Notes |
Date |
Text |
2010-12-22 14:41:11 | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. PROVIDE INFORMATION REGARDING DOOR SWING AND DOOR | | HARDWARE, FBC1008.1.9. PLEASE NOTE THAT THIS BUILDING | | IS ASSEMBLY OCCUPANCY. PLEASE ALSO PROVIDE ANY OTHER | | INFORMATION REQUIRED TO DETERMINE CODE COMPLIANCE, SUCH | | AS OCCUPANT LOAD. | | | | 2ND REVIEW, DOOR SWING PROVIDED BUT OCCUPANT LOAD AND | | HARDWARE (SUCH AS PANIC DEVICE) NOT PROVIDED. NOTE THAT | | THIS BUILDING IS ASSEMBLY OCCUPANCY, THEREFORE PANIC | | DEVICE REQUIRED WITH OCCUPANT LOAD OVER 50. EITHER | | REVISE PLAN TO SHOW HARDWARE OR PROVIDE MORE | | INFORMATION REGARDING OCCUPANT LOAD TO SHOW EXCEPTION. | | | | 2. OPENING FORCE TO COMPLY WITH FBC11-4.13.11(2)(A). | | | | 2ND REVIEW, LETTER FROM MANUFACTURER STATES (RESERVED) | | FOR OPENING FORCE FOR EXTERIOR DOORS (SEE ITEM 5 OF | | LETTER PROVIDED). MY UNDERSTANDING IS THAT THIS IS AN | | ADJUSTABLE FEATURE ON THE DOOR. PLEASE REVISE PLAN TO | | STATE OPENING FORCE. 8.5 MAX ALLOWED BY CODE. | | |
|