2010-12-22 14:41:11SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE INFORMATION REGARDING DOOR SWING AND DOOR
 HARDWARE, FBC1008.1.9. PLEASE NOTE THAT THIS BUILDING
 IS ASSEMBLY OCCUPANCY. PLEASE ALSO PROVIDE ANY OTHER
 INFORMATION REQUIRED TO DETERMINE CODE COMPLIANCE, SUCH
 AS OCCUPANT LOAD.
  
 2ND REVIEW, DOOR SWING PROVIDED BUT OCCUPANT LOAD AND
 HARDWARE (SUCH AS PANIC DEVICE) NOT PROVIDED. NOTE THAT
 THIS BUILDING IS ASSEMBLY OCCUPANCY, THEREFORE PANIC
 DEVICE REQUIRED WITH OCCUPANT LOAD OVER 50. EITHER
 REVISE PLAN TO SHOW HARDWARE OR PROVIDE MORE
 INFORMATION REGARDING OCCUPANT LOAD TO SHOW EXCEPTION.
  
 2. OPENING FORCE TO COMPLY WITH FBC11-4.13.11(2)(A).
  
 2ND REVIEW, LETTER FROM MANUFACTURER STATES (RESERVED)
 FOR OPENING FORCE FOR EXTERIOR DOORS (SEE ITEM 5 OF
 LETTER PROVIDED). MY UNDERSTANDING IS THAT THIS IS AN
 ADJUSTABLE FEATURE ON THE DOOR. PLEASE REVISE PLAN TO
 STATE OPENING FORCE. 8.5 MAX ALLOWED BY CODE.
  