Plan Review Notes
Plan Review Notes For Permit 10110288
Permit Number 10110288
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-11-30 17:04:14525 OKEECHOBEE BOULEVARD, SUITE #750
 PERMIT #10110288
 REVIEW COMMENTS - FIRE
  
 THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 USES THE 2006 EDITION OF THE LIFE SAFETY CODE - NFPA
 101 WITH FLORIDA AMENDMENTS. THE COVER SHEET REFERENCES
 THE 2003 EDITION OF NFPA 101.
  
 THE CURRENT EXIT ACCESS CONFIGURATION CREATES A COMMON
 PATH OF TRAVEL GREATER THAN 100 FEET. THE TWO DOORS
 (701 & 714) FROM THE TENANT SUITE ARE STILL CONSIDERED
 EXIT ACCESS AND NOT EXITS. OCCUPANTS EXITING THROUGH
 DOOR 714 WILL CONVERGE WITH THE OCCUPANTS EXITING
 THROUGH DOOR 701.
  
 PROVIDE PORTABLE FIRE EXTINGUISHER LOCATIONS ON THE
 FLOOR PLAN.
  
 TO OBTAIN A BUILDING PERMIT, CONSTRUCTION DOCUMENTS ARE
 NEEDED FOR THE MODIFICATION OF THE FIRE ALARM AND
 AUTOMATIC SPRINKLER SYSTEMS. ADDITIONALLY, SEPARATE
 PLANS AND PERMITS WILL BE NEEDED FOR THE FIRE ALARM AND
 SPRINKLER SYSTEM SHOP DRAWINGS.
  
 THE COLUMNS AND FURNITURE LAYOUT CREATE AN AISLE THAT
 IS LESS THAN 36 INCHES IN WIDTH ON SHEET A-1.1.
  
 THE ACCESS-CONTROLLED EGRESS SYSTEM SHALL BE INTEGRATED
 WITH THE BUILDING FIRE ALARM AND FIRE SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730