Plan Review Notes
Plan Review Notes For Permit 10110255
Permit Number 10110255
Review Stop B
Sequence Number 1
Notes
Date Text
2010-12-07 12:40:40****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC3105.1.1.1, RIGID FRAME CANNOT BE LESS THAN 7'6"
 FROM GRADE.
  
 2. ON THE PLAN, PLEASE CLARIFY USE. IF THIS IS A
 PASSENGER LOADING ZONE, SEE FBC11-4.6.5 (114" VERTICAL
 CLEARANCE REQUIRED).
  
 3. REVISE PLAN TO INCLUDE EXPOSURE CLASSIFICATION,
 FBC1603.1.4.
  