2010-11-09 13:43:18 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | 1- THERE ARE NOTES ON THE DRAWING SUBMITTED STATING | | THAT THE ROOF TURBINES ARE GOING TO BE REMOVED. THIS IS | | GOING TO AFFECT THE ROOF VENTILATION AS DESIGNED BY THE | | ORIGINAL DESIGNER OF RECORD. ROOF VENTILATION IS | | REQUIRED BY SEC. R806 OF 2007 FLORIDA RESIDENTIAL CODE. | | NEED A DESIGN PROFESSIONAL TO RE-DESIGN THE ATTIC | | VENTING REQUIREMENTS AS REQUIRED BY SEC. R806.1. |
|