Plan Review Notes
Plan Review Notes For Permit 10110254
Permit Number 10110254
Review Stop B
Sequence Number 1
Notes
Date Text
2010-11-08 17:20:51RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- FLAT ROOF NOA 07-0730.03 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. SEE MIAMI-DADE WEBSITE. NEED TO PROVIDE
 CURRENT NOA.
  
 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
 **NOTE: WHEN DOING THE CALCULATIONS TAKE INTO
 CONSIDERATION THAT THIS BUILDING IS LOCATED ON EXPOSURE
 "C".
  
 3- THERE ARE NOTES ON THE DRAWING SUBMITTED STATING
 THAT THE ROOF TURBINES ARE GOING TO BE REMOVED. THIS IS
 GOING TO AFFECT THE ROOF VENTILATION AS DESIGNED BY THE
 ORIGINAL DESIGNER OF RECORD. ROOF VENTILATION IS
 REQUIRED BY SEC. R806 OF 2007 FLORIDA RESIDENTIAL CODE.
 NEED A DESIGN PROFESSIONAL TO RE-DESIGN THE ATTIC
 VENTING REQUIREMENTS AS REQUIRED BY SEC. R806.1.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712