2010-11-05 15:04:48 | RESIDENTIAL (R3) ROOFING, BUILDING REVIEW CHECKLIST. |
| 2007 FBC WITH 2009 REVISIONS. |
| |
| 1- PERMIT APPLICATION CALLS FOR ROOF RECOVERY-REPAIRS. |
| NO MORE THAN 25% OF THE TOTAL ROOF AREA SHALL BE |
| REPAIRED OR RECOVERED UNLESS THE ENTIRE ROOFING SYSTEM |
| IS REPLACED. SEC. 611.1.1 OF FBC 2007- EXISTING |
| BUILDING CODE. |
| |
| 2- NOA 07-0822.10 SUBMITTED SI SUPERSEDED BY |
| MIAMI-DADE. SEE MIAMI-DADE WEBSITE. NEED TO PROVIDE |
| CURRENT NOA. |
| |
| 3- PROVIDE TWO COPIES OF NOA. ONLY ONE WAS SUBMITTED. |
| |
| 4- CLEARLY SPECIFY ON THE NEW NOA SUBMITTED WHICH |
| APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF |
| 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 5- A) IF SELECTED ASSEMBLY FROM THE NOA IS LIMITED BY |
| THE GENERAL LIMITATION #9, THEN IT MAY MAY NOT BE USED |
| IF THE DESIGN PRESSURES FOR THE SELECTED ASSEMBLY ARE |
| TOO LOW TO MEET THE REQUIREMENTS OF SEC. R301. GENERAL |
| LIMITATION #9 DOESN'T ALLOW NAIL ENHANCING. SEE GENERAL |
| LIMITATION #9 ON LAST PAGE OF NOA SUBMITTED. |
| |
| B) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| LIMITATION #7, THEN PROVIDE THE REQUIRED RAS 117 |
| CALCULATIONS FOR THE NAIL ENHANCING AT THE PERIMETER |
| AND CORNER AREAS. SEE GENERAL LIMITATION #7 ON LAST |
| PAGE OF NOA SUBMITTED TO CHECK IF THE REQUIRED RAS 117 |
| CALCULATIONS NEED TO BE SIGNED AND SEALED BY THE DESIGN |
| PROFESSIONAL. |
| |
| 6- ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 THIS |
| BUILDING IS LOCATED ON EXPOSURE "C". DESIGN |
| PROFESSIONAL DOING THE RAS 117 CALCULATIONS TO TAKE |
| THIS INTO CONSIDERATION WHEN DOING THE CALCULATIONS. |
| |
| 7- UPDATE VALUATION AS REQUIRED TO INCLUDE RE-ROOFING |
| ENTIRE ROOF. SEC. 108.3 CITY AMENDMENTS TO FBC. |
| |
| 8- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK |
| UP. |
| |