2011-05-03 10:42:27 | BUILDING PLAN REVIEW- |
| PERMIT: 08060519 |
| ADD: 309 CLEMATIS ST |
| CONT: WELLINGTON EQUESTRIAN |
| TEL: (561)312-6247 JOHN WEBB |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVISION: DENIED |
| |
| 1) THE SUBMITTED REVISION INDICATES A NEW AUTOMATIC |
| FIRE SHUTTER IN THE FRONT STAIRWELL BETWEEN THE 2ND AND |
| 3RD FLOOR. THIS FIRE SHUTTER LEADS TO AN AREA THAT CAN |
| BE CONSTRUED AS A MECHANICAL ROOM SINCE THIS WILL BE |
| THE DOORWAY TO WORK ON THE EXISTING MECHANICAL |
| EQUIPMENT BETWEEN THE EXISTING ROOFTOP AND THE NEW |
| THIRD FLOOR ROOF TOP ADDITION. |
| |
| THE PERMIT SET OF PLANS LS-1 OR A2.0 DATED REVISION# 3 |
| 5/11/09 DID NOT HAVE SUCH A DOORWAY IN THE VERTICAL |
| EXIT STAIRWELL. PLEASE REVIEW: |
| |
| 2004 FBC-B 1020.5 PENETRATIONS ALLOWED IN THE STAIRWELL |
| ARE LIMITED OR PROHIBITED EXCEPT FOR THE REQUIRED |
| EXITDOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR |
| INDEPENDENT PRESSURIZATION, SPRINKLER PIPING, |
| STANDPIPES, ELECTRIC RACEWAYS, FOR FIRE DEPARTMENT |
| COMMUNICATIONS AND ELECTRICAL RACEWAY SEERVING NOT MORE |
| THE EXIT PASSAGEWAY AND TERMINATING AT A STEEL BOX NOT |
| EXCEEDING 16 SQUARE INCHES. SUCH PENETRATIONS SHALL BE |
| PROTECTED IN ACCORDANCE WITH SECTION 712. |
| |
| THERE HAS BEEN MEETINGS ABOUT THIS PARTICULAR |
| SITUATION, AND THE AGREEMENT WAS TO HAVE A VESTIBULE |
| WITH TWO SETS OF 1 1/2 HR DOORS. THE INTENT WAS TO NOT |
| HAVE A MECHANICAL ROOM OPEN DIRECTLY INTO THE STAIRWELL |
| TRYING TO MEET THE INTENT OF 1020.5. |
| |
| JAMES A. WITMER C.B.O. |
| COMMERCIAL COMBINATION PLANS EXAMINER |