Plan Review Notes For Permit 10110181 |
Permit Number |
10110181 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-17 10:49:50 | 1920 WEKIVA WAY | | PERMIT NUMBER 10110181 | | GENERATOR INSTALLATION | | | | 1. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE | | NATIONAL ELECTRICAL CODE. | | | | 2. ENTIRE GENERATOR INSTALLATION TO COMPLY WITH NFPA | | 110. | | | | 3. PLANS DO NOT CONTAIN ANY STAMPS FROM THE DEPARTMENT | | OF ENVIRONMENTAL RESOURCE MANAGEMENT (DERM). | | | | 4. PLEASE PROVIDE AN APPROVED SURVEY OF THE PROPOSED | | PROPERTY WHERE THE GENERATOR IS TO BE INSTALLED. | | | | 5. APPROPRIATE SIGNAGE IS REQUIRED TO BE ON THE PLANS. | | THIS SIGNAGE SHALL INCLUDE THE NFPA 704 DIAMONDS, "NO | | SMOKING" SIGNS, PRODUCT NAME AND QUANTITY OF THE DIESEL | | FUEL. | | | | 6. PLEASE INDICATE ON THE PLANS WHAT EQUIPMENT THE | | GENERATOR IS EXPECTED TO RUN. IS IT LIFE SAFETY | | EQUIPMENT ONLY OR GENERAL LOADS OR BOTH AND PLEASE | | INDICATE DURATION. | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | | | | | |
|