2010-11-17 10:49:501920 WEKIVA WAY
 PERMIT NUMBER 10110181
 GENERATOR INSTALLATION
  
 1. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
 2. ENTIRE GENERATOR INSTALLATION TO COMPLY WITH NFPA
 110.
  
 3. PLANS DO NOT CONTAIN ANY STAMPS FROM THE DEPARTMENT
 OF ENVIRONMENTAL RESOURCE MANAGEMENT (DERM).
  
 4. PLEASE PROVIDE AN APPROVED SURVEY OF THE PROPOSED
 PROPERTY WHERE THE GENERATOR IS TO BE INSTALLED.
  
 5. APPROPRIATE SIGNAGE IS REQUIRED TO BE ON THE PLANS.
 THIS SIGNAGE SHALL INCLUDE THE NFPA 704 DIAMONDS, "NO
 SMOKING" SIGNS, PRODUCT NAME AND QUANTITY OF THE DIESEL
 FUEL.
  
 6. PLEASE INDICATE ON THE PLANS WHAT EQUIPMENT THE
 GENERATOR IS EXPECTED TO RUN. IS IT LIFE SAFETY
 EQUIPMENT ONLY OR GENERAL LOADS OR BOTH AND PLEASE
 INDICATE DURATION.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  