2010-11-23 07:52:53BUILDING PLAN REVIEW
 PERMIT: 10110181
 ADD: 1920 WEKIVA WAY
 CONT: J CROMPTON ELECTRIC, INC.
 TEL: (561)588-6559
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET T1 INDICATES THE WIND DESIGN CRITERIA AS A
 NORMAL DESIGN 3 SECOND GUST WIND VELOCITY 140 MPH. THE
 PLANS ARE LACKING THE WIND DESIGN CRITERIA AS TO:
  
 1609.6.2 WIND DESIGN PROCEDURES
 1.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 1.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4. PLEASE NOTE THIS IS A "C"
 EXPOSURE.
  
 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 1.5) DESIGNED AS OPEN, SEMI- ENCLOSED OR ENCLOSED.
  
 1.6 PRESSURES FOR DOOR OPENINGS.
  
 2) PLEASE PROVIDE THE LOCATION AND TYPE OF ANCHORS TO
 BE INSTALLED TO COUNTER THE MOMENT OF OVERTURNING AND
 SLIPPAGE, FBC-B 1604.4.
  
 3) MISSING PRODUCT APPROVALS FOR DOOR OPENINGS,
 REQUIRED BY RULE 9B-72.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved