2011-01-05 09:42:26PROVISO:
  
 1. PROVIDE CERTIFICATION FOR THE WIND LOAD ON THE LIGHT
 POLES FROM THE MANUFACTURER WITH ACCEPTANCE FROM THE
 ENGINEER OF RECORD.
 2. PROVIDE VERIFICATION THE MOTOR CONTROL CENTERS ARE
 LISTED BY A NATIONALLY RECOGNIZED TEST AGENCY ( NRTL).
 VERIFY ALL ELECTRICAL EQUIPMENT EXPOSED TO WATER VAPOR
 AND SPRAY IS LISTED FOR WET LOCATIONS. NEC 2008 110-3
 3. THE CONSTRUCTION VALUE DOES NOT ACCURATELY REFLECT
 THE COMPLETE CONSTRUCTION COSTS INCLUDING CAR WASH
 EQUIPMENT. PLEASE ADJUST.
  
 R. LECKY, ELECTRIC PLAN REVIEW, 561-805-6718
  
  