Plan Review Notes
Plan Review Notes For Permit 10110159
Permit Number 10110159
Review Stop B
Sequence Number 2
Notes
Date Text
2011-01-19 19:43:57***PROVISOS***
  
 1. PROVIDE ORIGINAL SOILS INVESTIGATION REPORT (PRIOR
 TO ISSUANCE)
  
 2. SUBMIT DOOR PRODUCT APPROVALS (METAL DOOR, METAL
 LOUVERED DOOR) - REVISION REQUIRED.
  
 3. SEPARATE ROOF PERMIT REQUIRED. THE FOLLOWING ROOF
 PRODUCT APPROVALS WERE REVIEWED BY D.O.R.:
  
 NOA 08-0410.08, PAGE 17
 NOA 07-1217.01, PAGE 26-27
 NON HVHZ NOA 06-0713.03
  
 SEPARATE PERMIT REQUIRED FOR ROOF. THE FOLLOWING
 INFORMATION IS TO BE SUBMITTED WITH ROOF PERMIT
 APPLICATION:
  
 COMPONENT & CLADDING DESIGN PRESSURES FOR ROOF (FLAT
 AND PITCHED)
 ALL DELEGATED ENGINEERING IS TO BE REVIEWED BY DESIGNER
 OF RECORD PRIOR TO SUBMITTAL (E.KUONEN, PE OR
 M.MANGONE, ARCHITECT)
 FOR FLAT ROOFS, METHOD OF ATTACHMENT TO BE SELECTED
 FROM APPROVED ASSEMBLY
 FOR FLAT ROOFS, RAS117 CALCULATIONS PREPARED BY AN
 ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT FOR
 ENHANCED FASTENING (SEE GENERAL LIMITATION #7)
 FOR THE TILE ROOF, SELECT METHOD OF ATTACHMENT FROM
 FRSA/TRI 07320 TO SHOW COMPLIANCE WITH UPLIFT
 REQUIREMENTS
  
 4. PROVIDE IMPACT FEE RECEIPT (PRIOR TO ISSUANCE)
  
 5. PROVIDE A COPY OF THE CONTRACT. VALUE IS TO INCLUDE
 LABOR AND MATERIALS (INCLUDING ANY PERMANENTLY
 INSTALLED EQUIPMENT).
  
  