Plan Review Notes
Plan Review Notes For Permit 10110159
Permit Number 10110159
Review Stop P
Sequence Number 1
Notes
Date Text
2010-11-20 11:52:01FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. THE RESTROOM FOR THE EMPLOYEES IS REQUIRED TO BE ADA
 ACCESSABLE.
 11-4.1.3(11) TOILET FACILITIES. IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22.
  
 2.. P-1 SHOWS 6" SANITARY CONTINUING TO SOUTH SIDE OF
 BUILDING WITH THE NOTE "SEE SHEET P-2 FOR
 CONTINUATION". SHEET P-2 DOES NOT SHOW A CONTINUATION
 TO THE SOUTH SIDE OF THE BUILDING.
  
 3. BACKFLOW PROTECTION MAY BE REQUIRED WHERE FEEDING
 CAR WASH EQUIPMENT DEPENDING ON THE HAZARD RISK.
 FBC PLUMBING 2007 608.16.6 CONNECTIONS SUBJECT TO
 BACKPRESSURE. WHERE A POTABLE WATER CONNECTION IS MADE
 TO A NONPOTABLE LINE, FIXTURE, TANK, VAT, PUMP OR OTHER
 EQUIPMENT SUBJECT TO BACK-PRESSURE, THE POTABLE WATER
 CONNECTION SHALL BE PROTECTED BY A REDUCED PRESSURE
 PRINCIPLE BACKFLOW PREVENTER.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  