Plan Review Notes For Permit 10110159 |
Permit Number |
10110159 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-20 11:52:01 | FBC PLUMBING 2007 REVIEW #1 | | DENIED: | | | | 1. THE RESTROOM FOR THE EMPLOYEES IS REQUIRED TO BE ADA | | ACCESSABLE. | | 11-4.1.3(11) TOILET FACILITIES. IF TOILET ROOMS ARE | | PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM | | SHALL COMPLY WITH SECTION 11-4.22. | | | | 2.. P-1 SHOWS 6" SANITARY CONTINUING TO SOUTH SIDE OF | | BUILDING WITH THE NOTE "SEE SHEET P-2 FOR | | CONTINUATION". SHEET P-2 DOES NOT SHOW A CONTINUATION | | TO THE SOUTH SIDE OF THE BUILDING. | | | | 3. BACKFLOW PROTECTION MAY BE REQUIRED WHERE FEEDING | | CAR WASH EQUIPMENT DEPENDING ON THE HAZARD RISK. | | FBC PLUMBING 2007 608.16.6 CONNECTIONS SUBJECT TO | | BACKPRESSURE. WHERE A POTABLE WATER CONNECTION IS MADE | | TO A NONPOTABLE LINE, FIXTURE, TANK, VAT, PUMP OR OTHER | | EQUIPMENT SUBJECT TO BACK-PRESSURE, THE POTABLE WATER | | CONNECTION SHALL BE PROTECTED BY A REDUCED PRESSURE | | PRINCIPLE BACKFLOW PREVENTER. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|