2010-12-10 07:56:47SEPARATE SUBMITTAL IS REQUIRED TO:
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 WWW.WPB.ORG/ENGINEERING
 PLEASE GO TO THE LINK BELOW,
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP
 DEVELOPMENT PERMIT PACKAGE 2010
 WILL GIVE YOU INSTRUCTIONS AND DOCUMENTATION REQUIRED
 FOR YOUR SUBMITTAL.
  
 SPECIFIC SITE COMMENTS:
 #1 WATER SERVICE TO THE PROPERTY IS 3/4" DIAMETER
 COPPER LINE.
 PLANS CALL FOR A 2". NEW TAP MAY BE REQUIRED BASED ON
 YOUR WATER DEMAND
 CALCULATION. (PLEASE SUPPLY DOCUMENTATION WITH PEAK
 WATER DEMAND).
 PLEASE TAKE INTO ACCOUNT CAR WASH EQUIPMENT, PUMPS,
 TANKS, ETC.)
  
 #2 BACKFLOWS ARE REQUIRED TO BE AS CLOSE TO THE SOURCE
 METER AS POSSIBLE,
 18" MAX DISTANCE.
  
 #3 SEPERATE WATER SERVICE FOR IRRIGATION IS RECOMMENED
 AS SEWAGE PROCESSING
 WILL BE CHARGE BASED ON DOMESTIC WATER METER
 CONSUPTION.
  
 #4 PROVIDE A "SURFACE WATER MANAGEMENT REPORT".
  
 #5 SOUTHERN BLVD IS AN FDOT ROAD, PERMIT FOR UTILITY
 INSTALLTION MAY BE REQUIRED.
 DRIVEWAY ENTRANCE MODIFICATIONS WILL ALSO REQUIRE
 PERMITTING.
  
 #6 THE DRIVEWAY ON OLIVE AVE WILL REQUIRE TRUNCATED
 DOMES (ADA) ON EITHER SIDE.
 2' WIDE X THE FULL WIDTH OF SIDEWALK.
  
 #7 ON SHEET C1, SHEET 1 OF 10 YOU CALL OUT SECTION AA,
 SECTION BB, AND SECTION DD HOWEVER IT SEEMS TO BE
 MISSING.
 PLEASE MAKE REFERENCE THAT THEY APPEAR ON SHEET C8,
 SHEET 8 OF 10.
  
 #8 PERVIOUS PAVER SYSTEM IS NOT AN APPROVED METHOD OF
 DRAINAGE WITHIN THE CITY OF WPB.
 SUPPLY ALTERNATE SYSTEM OF DRAINAGE.
  
 #9 A NEW CLEAN-OUT NEEDS TO BE INSTALLED AT CONNECTION
 POINT AND AT EVERY 75'.
 ANOTHER CLEAN-OUT JUST AFTER PIPE EXITS BUILDING.
 PIPE COLOR CODED TO DESIGNATE SEWAGE.
  
 #10 PROVIDE ENVIRONMENTAL SUMMARY OF SITE PREVIOUS USE
 AND IF ANY ENVIRONMENTAL REMEDIATION IS REQUIRED.
 (FOR EXAMPLE EXISTING UNDERGROUND TANKS, WELL POINTS,
 MONITORING WELLS, ETC.)
  
 #11 PROVIDE INFORMATION ON CARWASH SYTEM OR SUMMARY
 DESCRIBING PUMPS, TANKS, CISTERNS, ALL INTERNAL
 PROCESSES, ETC
  
 #12 IDENTIFY LOCATION OF "DRYWELL" ON THE CIVIL PLANS.
  
 #13 WHERE DO ROOF DRAINS DISCHARGE TO?
  
 #14 PROVIDE CITY STANDARD BACKFLOW DETAIL. STANDARD
 SIDEWALK DETAILS, ETC
  
 #15 PLEASE INCLUDE PERVIOUS AND IMPERVIOUS TOTALS
 (SF,AC) ON PAVING PLAN C1, SHEET 1 OF 10.
  
 PLEASE, RESPOND TO ALL COMMENTS IN WRITING. THANKS!
 *******************************************************
 **********************************************
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved