Plan Review Notes
Plan Review Notes For Permit 10110159
Permit Number 10110159
Review Stop E
Sequence Number 1
Notes
Date Text
2010-12-08 08:50:161. DESIGNATE ON THE PLAN THE METHOD INTENDED TO PROVIDE
 A DEDICATED ELECTRICAL EQUIPMENT SPACE WITH SAFETY
 CLEARANCES FOR THE ELECTRICAL PANELS AND TRANSFORMER.
 NEC 110.26
 2. PROVIDE GFCI PROTECTION FOR THE DRINKING FOUNTAIN.
 NEC 2008
 3. PROVIDE AN INTERSYSTEM BONDING TERMINATION AT THE
 MAIN SERVICE EQUIPMENT. NEC 250-94
 4. PROVIDE COMPLIANCE DETAIL ON THE PLANS FOR LIGHTING
 AND OTHER ELECTRICAL SYSTEMS AS IDENTIFIED WITHIN THE
 FLORIDA BUILDING CODE ( FBC) REQUIREMENTS FOR ENERGY
 CONSERVATION. INCLUDE LIGHTING DENSITIES. FBC 2007,
 SECTION 13-413
 5. PROVIDE CERTIFICATION FOR THE WIND LOAD ON THE LIGHT
 POLES. PROVIDE SIGNED AND SEALED CONSTRUCTION DETAIL.
 6. PROVIDE VERIFICATION THE MOTOR CONTROL CENTERS ARE
 LISTED BY A NATIONALLY RECOGNIZED TEST AGENCY ( NRTL).
 VERIFY ALL ELECTRICAL EQUIPMENT EXPOSED TO WATER VAPOR
 AND SPRAY IS LISTED FOR WET LOCATIONS. NEC 2008 110-3
 7. THE CONSTRUCTION VALUE DOES NOT ACCURATELY REFLECT
 THE COMPLETE CONSTRUCTION COSTS INCLUDING CAR WASH
 EQUIPMENT. PLEASE ADJUST.
  