Plan Review Notes For Permit 10110159 |
Permit Number |
10110159 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-12-08 08:50:16 | 1. DESIGNATE ON THE PLAN THE METHOD INTENDED TO PROVIDE | | A DEDICATED ELECTRICAL EQUIPMENT SPACE WITH SAFETY | | CLEARANCES FOR THE ELECTRICAL PANELS AND TRANSFORMER. | | NEC 110.26 | | 2. PROVIDE GFCI PROTECTION FOR THE DRINKING FOUNTAIN. | | NEC 2008 | | 3. PROVIDE AN INTERSYSTEM BONDING TERMINATION AT THE | | MAIN SERVICE EQUIPMENT. NEC 250-94 | | 4. PROVIDE COMPLIANCE DETAIL ON THE PLANS FOR LIGHTING | | AND OTHER ELECTRICAL SYSTEMS AS IDENTIFIED WITHIN THE | | FLORIDA BUILDING CODE ( FBC) REQUIREMENTS FOR ENERGY | | CONSERVATION. INCLUDE LIGHTING DENSITIES. FBC 2007, | | SECTION 13-413 | | 5. PROVIDE CERTIFICATION FOR THE WIND LOAD ON THE LIGHT | | POLES. PROVIDE SIGNED AND SEALED CONSTRUCTION DETAIL. | | 6. PROVIDE VERIFICATION THE MOTOR CONTROL CENTERS ARE | | LISTED BY A NATIONALLY RECOGNIZED TEST AGENCY ( NRTL). | | VERIFY ALL ELECTRICAL EQUIPMENT EXPOSED TO WATER VAPOR | | AND SPRAY IS LISTED FOR WET LOCATIONS. NEC 2008 110-3 | | 7. THE CONSTRUCTION VALUE DOES NOT ACCURATELY REFLECT | | THE COMPLETE CONSTRUCTION COSTS INCLUDING CAR WASH | | EQUIPMENT. PLEASE ADJUST. | | |
|