Plan Review Notes
Plan Review Notes For Permit 10110105
Permit Number 10110105
Review Stop B
Sequence Number 1
Notes
Date Text
2010-11-30 09:54:39RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- APPROVED ASSEMBLY ON PAGE 8 SELECTED ON NOA
 07-0730.03 SUBMITTED CAN'T BE USED BECAUSE IT DOESN'T
 MEET THE DESIGN PRESSURES FOR THIS BUILDING. ALSO, THIS
 ASSEMBLY IS LIMITED BY GENERAL LIMITATION #9 WHICH
 DOESN'T ALLOW NAIL ENHANCING. SEE GENERAL LIMITATION #9
 ON LAST PAGE OF NOA SUBMITTED.
 SELECT ANOTHER ASSEMBLY THAT IS LIMITED BY GENERAL
 LIMITATION #7 AND PROVIDE THE RESPECTIVE RAS 117
 CALCULATIONS FOR NAIL ENHANCING.
 ***NOTE: THIS BUILDING IS LOCATED ON EXPOSURE "C".
  
 2- ACCORDING TO MIAMI-DADE WEBSITE NOA 07-0730.03
 SUBMITTED WAS SUPERSEDED. NEED TO PROVIDE CURRENT NOA
 09-0820.11.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712