2010-12-22 16:06:012007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) PROVIDE A DETAIL OF THE ONE HOUR FIRE WALL AND ATTIC
 SEPARATION BETWEEN THE TWO UNITS SHOWING COMPLIANCE
 WITH FBC R317.1.
  
 2) SHOW COMPLIANCE WITH N1102.AB.1.1 OF THE FLORIDA
 ENERGY CODE FOR INSULATION OF THE COMMON WALL BETWEEN
 THE TWO CONDITIONED TENANCIES.
  
 3) THE ENERGY CALCULATION FORMS LIST THE ATTIC
 INSULATION AS R-30 AND THE PLANS SPECIFY R-19. PLEASE
 CORRECT. THE ENERGY CALCS. DO NOT LIST THE COMMON WALL
 INSULATION. PLEASE CORRECT. THE ENERGY CALC. FORMS ARE
 REQUIRED TO BE SIGNED BY THE OWNER/AGENT. PLEASE
 CORRECT.
  
 4) PROVIDE A WALL SECTION/DETAIL OF THE NON-LOAD
 BEARING INTERIOR WALLS ON THE PLANS.
  
 5) THE DESIGN CRITERIA ON SHEET 1 OF THE PLANS SPECIFY
 EXPOSURE CATEGORY B AND PER FBC R301.2.1.4.3 THE
 STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]