Plan Review Notes For Permit 10110061 |
Permit Number |
10110061 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-12-22 16:06:01 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) PROVIDE A DETAIL OF THE ONE HOUR FIRE WALL AND ATTIC | | SEPARATION BETWEEN THE TWO UNITS SHOWING COMPLIANCE | | WITH FBC R317.1. | | | | 2) SHOW COMPLIANCE WITH N1102.AB.1.1 OF THE FLORIDA | | ENERGY CODE FOR INSULATION OF THE COMMON WALL BETWEEN | | THE TWO CONDITIONED TENANCIES. | | | | 3) THE ENERGY CALCULATION FORMS LIST THE ATTIC | | INSULATION AS R-30 AND THE PLANS SPECIFY R-19. PLEASE | | CORRECT. THE ENERGY CALCS. DO NOT LIST THE COMMON WALL | | INSULATION. PLEASE CORRECT. THE ENERGY CALC. FORMS ARE | | REQUIRED TO BE SIGNED BY THE OWNER/AGENT. PLEASE | | CORRECT. | | | | 4) PROVIDE A WALL SECTION/DETAIL OF THE NON-LOAD | | BEARING INTERIOR WALLS ON THE PLANS. | | | | 5) THE DESIGN CRITERIA ON SHEET 1 OF THE PLANS SPECIFY | | EXPOSURE CATEGORY B AND PER FBC R301.2.1.4.3 THE | | STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C. PLEASE | | CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|