2010-11-10 19:19:20**********PLAN REVIEW FAIL***********
  
 1) PROVIDE LIGHTING DENSITIES AS PER ARTICLE 13-415
 ABC. 2007 F.B.C.
 2) AUTOMATIC LIGHTING CONTROLS REQUIRED AS PER ARTICLE
 13-415.ABC.1.1 2007 F.B.C.
 3) COMPLY WITH ARTICLE 220.87 2008 N.E.C. FOR ADDING
 NEW LOADS TO EXISTING PANELS.
 4) BATTERY BACK UP REQUIRED FOR EMERGENCY LIGHTING
 LUMIAIRS ON EMERGENCY CIRCUITRY ARTICLE 1006.2.3.2 2007
 F.B.C.
 5) CAN USE ARTICLE 220.16(B) 2008 N.E.C. FOR ADDING NEW
 LOADS TO EXISTING PANELS ON 3RD AND 4TH FLOORS.
  