Plan Review Notes For Permit 10110055 |
Permit Number |
10110055 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-10 19:19:20 | **********PLAN REVIEW FAIL*********** | | | | 1) PROVIDE LIGHTING DENSITIES AS PER ARTICLE 13-415 | | ABC. 2007 F.B.C. | | 2) AUTOMATIC LIGHTING CONTROLS REQUIRED AS PER ARTICLE | | 13-415.ABC.1.1 2007 F.B.C. | | 3) COMPLY WITH ARTICLE 220.87 2008 N.E.C. FOR ADDING | | NEW LOADS TO EXISTING PANELS. | | 4) BATTERY BACK UP REQUIRED FOR EMERGENCY LIGHTING | | LUMIAIRS ON EMERGENCY CIRCUITRY ARTICLE 1006.2.3.2 2007 | | F.B.C. | | 5) CAN USE ARTICLE 220.16(B) 2008 N.E.C. FOR ADDING NEW | | LOADS TO EXISTING PANELS ON 3RD AND 4TH FLOORS. | | | | JOHN DICKINSON | | CONTRACT PLANS EXAMINER LICENSE NUMBER PX3182 | | CELL PHONE 561-718-3230 |
|