Plan Review Notes
Plan Review Notes For Permit 10110043
Permit Number 10110043
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-11-03 15:33:23505 SOUTH FLAGLER DRIVE SUITE #700
 PERMIT #10110043
 MASTER #10080742
  
 REVIEW COMMENTS - FIRE
  
 1) SPRINKLER SPRAY (X2) IS OBSTRUCTED BY 31-INCH WIDE
 SOFFIT FEATURED AT EAST/WEST AREA OF CONFERENCE ROOM
 #701. SOFFIT IS LOCATED 7-INCHES BELOW SPRINKLER
 ELEVATION.
  
 2) ARMOVERS EXCEEDING 12-INCHES IN LENGTH REQUIRE
 HANGERS WHEN SYSTEM PRESSURES EXCEED 100 PSI.
  
 3) SYSTEM PRESSURES EXCEEDING 100 PSI REQUIRE HANGERS
 (OR ALL-THREAD ROD) TO PREVENT UPWARD MOVEMENT OF END
 SPRINKLERS OR ARMOVERS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730