2010-11-19 13:56:241000 45TH STREET
 HOMELESS RESOURCE CENTER
 REVIEW COMMENTS - FIRE
 PERMIT #10110012
 PERMIT #10110013
 PERMIT #10110014
  
 *****APPROVED PROVISO*****
  
 SUBMIT BATTERY CALCULATIONS.
  
 DUCT SMOKE DETECTORS SHALL CAUSE A GENERAL FIRE ALARM.
  
 SYSTEM SHALL BE MONITORED BY A THIRD PARTY LISTED BY
 UL.
  
 COORDINATE/MONITOR FIRE SPRINKLER SYSTEM FLOW AND
 TAMPER SWITCH LOCATIONS AND BACKFLOW PREVENTER TAMPER
 SWITCHES.
  
 SMOKE DETECTOR IS NOT PERMITTED AT THE TOP OF THE
 ELEVATOR SHAFT UNLESS A FIRE SPRINKLER IS LOCATED AT
 THE TOP THE SHAFT.
  
 BUILDING 2 ONLY SHOWS A STROBE DEVICE AND TWO EXTERIOR
 HORN/STROBE DEVICES. PLEASE EXPLAIN LACK OF PULL
 STATIONS AND OTHER FIRE ALARM DEVICES.
  