2010-11-10 15:25:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. WINDOWS ARE MARKED AS "EGRESS" ON THE PLAN BUT ARE
 50" HIGH SO DO NOT COMPLY WITH EGRESS REQUIREMENTS, FBC
 R310. PLEASE SEE EXCEPTION, FBC EB 604.1. THE CLEAR
 OPENING CANNOT BE REDUCED BY MORE THAN 5%. PROVIDE
 INFORMATION REGARDING EXISTING BEDROOM WINDOWS (TYPE OF
 WINDOW SUCH AS AWNING, JALOUSY, SINGLE HUNG, CASEMENT).