Plan Review Notes
Plan Review Notes For Permit 10100677
Permit Number 10100677
Review Stop B
Sequence Number 1
Notes
Date Text
2010-11-01 14:46:16BUILDING PLAN REVIEW
 PERMIT: 10100677
 ADD: 255 EVERNIA # SUITE 1203
 CONT: ROOF DOCTOR
 TEL: 772621-0508
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE CLARIFY THE SCOPE OF WORK TO BE COMPLETED
 UNDER THIS PERMIT. THE APPLICARTION INDICATES A
 PATICULAR SUITE BUT THE ENGINEERS REPORT INDICATES TO
 CORRECT THE PROBLEM OF WATER INTRUSION THAT THE WHOLE
 TILE FLOOR WOULD NEED TO BE REMOVED CLEANED DOWN TO THE
 CONCRETE DECK AND START OVER, PLEASE REVIEW THE REPORT
 FROM DANIEL J. MOSS P.E.
  
 2) IF WORK IS TO BE COMPLETED UNDER THE COMMON AREAS
 AND INDIVIDUAL SUITES TTHE TRUNKATED PCN IS
 74-43-43-22-37 THIS ABREVIATED PCN INDICATES THIS TO BE
 A COMMON AREA.
  
 3) THE SQUARE FOOTAGE TO BE REWORKED WILL ALSO NEED TO
 BE INDICATED ON THE PERMIT APPLICATION, THE VALUE OF
 $2,000.00 IS EXTREMELY LOW.
  
 4) MISSING PRODUCT APPROVALS FOR THE ROOFING SYSTEM.
 THE APPROVALS NEED TO BE REVIEWED BY THE DESIGNER OF
 RECORD AND SHOP DRAWING STAMP AFFIXED.
 RULE 9B-72(31) REQUIRES PRODUCT APPROVALS FOR ROOFING
 SYSTEMS.
  
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) 1609.6.2 WIND DESIGN PROCEDURES
 5.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 5.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved