2010-11-01 14:46:16 | BUILDING PLAN REVIEW |
| PERMIT: 10100677 |
| ADD: 255 EVERNIA # SUITE 1203 |
| CONT: ROOF DOCTOR |
| TEL: 772621-0508 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLEASE CLARIFY THE SCOPE OF WORK TO BE COMPLETED |
| UNDER THIS PERMIT. THE APPLICARTION INDICATES A |
| PATICULAR SUITE BUT THE ENGINEERS REPORT INDICATES TO |
| CORRECT THE PROBLEM OF WATER INTRUSION THAT THE WHOLE |
| TILE FLOOR WOULD NEED TO BE REMOVED CLEANED DOWN TO THE |
| CONCRETE DECK AND START OVER, PLEASE REVIEW THE REPORT |
| FROM DANIEL J. MOSS P.E. |
| |
| 2) IF WORK IS TO BE COMPLETED UNDER THE COMMON AREAS |
| AND INDIVIDUAL SUITES TTHE TRUNKATED PCN IS |
| 74-43-43-22-37 THIS ABREVIATED PCN INDICATES THIS TO BE |
| A COMMON AREA. |
| |
| 3) THE SQUARE FOOTAGE TO BE REWORKED WILL ALSO NEED TO |
| BE INDICATED ON THE PERMIT APPLICATION, THE VALUE OF |
| $2,000.00 IS EXTREMELY LOW. |
| |
| 4) MISSING PRODUCT APPROVALS FOR THE ROOFING SYSTEM. |
| THE APPROVALS NEED TO BE REVIEWED BY THE DESIGNER OF |
| RECORD AND SHOP DRAWING STAMP AFFIXED. |
| RULE 9B-72(31) REQUIRES PRODUCT APPROVALS FOR ROOFING |
| SYSTEMS. |
| |
| 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 5) 1609.6.2 WIND DESIGN PROCEDURES |
| 5.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| |
| 5.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| ACCORDANCE WITH SECTION1609.5. |
| |
| 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4. |
| |
| 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |