Plan Review Notes
Plan Review Notes For Permit 10100660
Permit Number 10100660
Review Stop E
Sequence Number 1
Notes
Date Text
2010-11-01 17:08:18************ELECT DENIED*************
 1)PAPER WORK FOR ATS DOES NOT SHOW A UL OR OTHER
 APPROVED TEST LAB.
 2) SUBMIT A RISER DIAGRAM SHOWING ALL MAIN SERVICE
 ELECTRICAL EQUIPMENT.
 3) ELECTRICAL PLAN IS REQUIRED TO HAVE DESIGNERS NAME,
 LICENSE MUMBER,AND BE SIGNED
 4) SHOW LOADS BEING SERVED
 5) SUBMIT LOAD CALCUATIONS ON GENERATOR
 6) SUBMIT SERVEY SITE PLAN SHOWING GENERATOR LOCATION
 AND EXHUST IN REFERANCE TO ANY BUILDING OPENINGS
 DOORS,WINDOWS,VENTS.