Plan Review Notes For Permit 10100660 |
Permit Number |
10100660 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-01 17:08:18 | ************ELECT DENIED************* | | 1)PAPER WORK FOR ATS DOES NOT SHOW A UL OR OTHER | | APPROVED TEST LAB. | | 2) SUBMIT A RISER DIAGRAM SHOWING ALL MAIN SERVICE | | ELECTRICAL EQUIPMENT. | | 3) ELECTRICAL PLAN IS REQUIRED TO HAVE DESIGNERS NAME, | | LICENSE MUMBER,AND BE SIGNED | | 4) SHOW LOADS BEING SERVED | | 5) SUBMIT LOAD CALCUATIONS ON GENERATOR | | 6) SUBMIT SERVEY SITE PLAN SHOWING GENERATOR LOCATION | | AND EXHUST IN REFERANCE TO ANY BUILDING OPENINGS | | DOORS,WINDOWS,VENTS. | | JOHN DICKINSON | | CONTRACT PLAN REVIEWER CITY OF WEST PALM BEACH | | CELL PHONE 561-718-3232 | | |
|