Plan Review Notes For Permit 10100660 |
Permit Number |
10100660 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-22 17:21:13 | BUILDING PLAN REVIEW | | PERMIT: 10100660 | | ADD: 804 2ND ST | | CONT: POWER PRO-TECH SERVICES, INC | | TEL: (561)859-1523 | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | W/ 2009 FBC SUPPLEMENTS | | * WEST PALM BEACH AMENDMENTS | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST BUILDING REVIEW | | ACTION: DENIED | | | | 1) THIS IS A REPLACEMENT GENERATOR LOCATED OUTSIDE OF | | ANY STRUCTURE, PLANS FAIL TO IDENTIFY WIND DESIN | | CRITERIA: | | 1609.6.2 WIND DESIGN PROCEDURES | | 1.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN | | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE | | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. | | | | 1.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN | | ACCORDANCE WITH SECTION1609.5. | | | | 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN | | ACCORDANCE WITH 1609.4. | | | | 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * | | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) | | | | 2) PLANS FAIL TO IDENTIFY HOW THE GENERATOR WILL BE | | INSTALLED (ANCHORED) TO RESIST THE MOMENT OF | | OVERTURNING AND OR SLIPPING | | FBC-B 1604.3.6 & 1609. | | | | | | JIM WITMER C. B. O. | | COMMERCIAL COMBINATION PLAN REVIEW | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] |
|