Plan Review Notes For Permit 10100644 |
Permit Number |
10100644 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-02 16:10:21 | PLANS DENIED | | 1) NEED SIGNATURE AND LIC.NUMBER OF AIRCONDITIONING | | CONTRACTOR ON THE PLANS . | | 2) NEED GRILL SIZE AND CFM ON ALL SUPPLY GRILLS . | | 3) NEED A SIGNATURE ON THE ENERGY CALCULATIONS. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | |
|