Plan Review Notes For Permit 10100640 |
Permit Number |
10100640 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-03 08:54:05 | 3111 SOUTH DIXIE HIGHWAY SUITE #220 | | PERMIT #10100640 | | MASTER #10050733 | | | | REVIEW COMMENTS - FIRE | | | | 1) SPRINKLER COVERAGE OBSTRUCTED BY WALL IN WAITING | | ROOM #200 (WEST AREA BY STAIR). | | | | 2) VERIFY SMALL ROOM INSIDE FILE ROOM #280 IS A SHAFT | | AND NOT A CLOSET REQUIRING SPRINKLER PROTECTION. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | 561-805-6730 |
|